6. Electrical work
6.4. Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example) (Fig. 6-4)
A
: Switch (Breakers for Wiring and Current Leakage (if you use))
B
: Outdoor Unit
C
: Pull Box
D
: Indoor Unit
Fig. 6-4
D
D
C
A
D
D
A
B
C
D
TB7
TB3
IC
(51)
TB5
(01)
IC
TB5
(03)
IC
TB5
(02)
IC
TB5
(04)
L
2
L
1
(101)
RC
RC
(104)
OC
TB7
(53)
OC
L
3
L
6
L
7
L
4
1
H
r
M1 M2 S M1 M2 S
M1 M2 S
M1 M2 S
A B
M1 M2 S
M1 M2 S
S
M1 M2 S
TB3
M1 M2 S
M1 M2 S
A B
M1 M2
H
IC
TB5
(05)
IC
TB5
(07)
IC
TB5
(06)
M1 M2 S
M1 M2 S
M1 M2 S
(105)
RC
(155)
RC
A B
A B
G
F
2
r
3
r
A
C
B
D
TB7
IC
(51)
TB15
TB15
TB15
MA
(01)
IC
TB5
(03)
IC
TB5
TB5
(02)
IC
TB5
(04)
L
1
MA
OC
(53)
OC
L
3
L
7
L
4
m
3
1
1
2
TB3
m
m
m
M1 M2 S M1 M2 S
TB7
M1 M2 S
M1 M2 S
TB3
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
A B
1 2
1 2
M1 M2 S
1 2
1 2
TB15
A B
L
2
L
6
H
H
IC
(05)
IC
(07)
IC
(06)
MA
MA
1
2
m
m
TB15
TB5
M1 M2 S
1 2
TB15
TB5
M1 M2 S
1 2
A B
A B
TB5
M1 M2 S
1 2
TB15
G
E
F
E
3
m
4
m
■
MA Remote Controller
Fig. 6-2
Fig. 6-3
■
M-NET Remote Controller
Thickness of Wire for Main Power Supply and On/Off Capacities
Model
Power Supply
Minimum Wire Thickness
(mm
2
[AWG])
Conduit
Size
Breaker for
Wiring*1
Breaker for Current Leakage
(if you use)
Minimum cir-
cuit ampacity
Maximum rating of over
current protector device
Main Cable*2
Ground
Outdoor Unit
P36/48
208/230 V AC,
60 Hz
5.3 [AWG10] 5.3 [AWG10] 3/4 inch *3
30 A
30 A 30 mA 0.1 sec. or less
29 A
44 A
HP36/48
8.4 [AWG8]
8.4 [AWG8]
3/4 inch
40 A
40 A 30 mA 0.1 sec. or less
36 A
44 A
P60
8.4 [AWG8]
8.4 [AWG8]
3/4 inch
40 A
40 A 30 mA 0.1 sec. or less
36 A
45 A
Indoor Unit
Refer to installation manual of indoor unit.
*1. Please follow applicable federal, state, or local codes to prevent potential leakage/electric shock. Or install a ground fault interrupt for the prevention of leakage and
electric shock.
IMPORTANT
If a current leakage breaker is used, it should be compatible with higher harmonics as this unit is equipped with an inverter. The use of an inadequate breaker
can cause the incorrect operation of inverter.
*2. Use copper supply wires. Use the electric wires over the rating voltage 300 V.
*3. Although the conduit size is larger than the size specified for the wire thickness according to UL standards, use a conduit size of 3/4 inch.
208/230 V AC
60 Hz
208/230 V AC
60 Hz
A
B
GR
Power Supply
Unit
Power Supply
Unit
System
controller
System
controller
<Permissible Lengths>
• Max length via outdoor units: L
1
+L
2
+L
3
+L
4
, L
3
+L
4
+L
6
+L
7
and
L
1
+L
2
+L
6
+L
7
500 m [1640 ft] (1.25 mm
2
[AWG16] or more)
• Max transmission cable length: L
1
, L
3
+L
4
, L
2
+L
6
and L
7
200
m [656 ft] (1.25 mm
2
[AWG16] or more)
• Remote controller cable length:
ℓ
1
,
ℓ
2
+
ℓ
3
10 m [33 ft] (0.5 to 1.25 mm
2
[AWG20 to AWG16])
If the length exceeds 10 m [33 ft], use a 1.25 mm
2
[AWG16]
shielded wire. The section of the cable that exceeds 10 m
[33 ft] must be included in the max length via outdoor units
and max transmission cable length.
<Permissible Lengths>
• Max length via outdoor unit (M-NET cable): L
1
+L
2
+L
3
+L
4
,
L
3
+L
4
+L
6
+L
7
and L
1
+L
2
+L
6
+L
7
500 m [1640 ft] (1.25 mm
2
[AWG16] or more)
• Max transmission cable length (M-NET cable): L
1,
L
3
+L
4,
L
2
+L
6
and L
7
200 m [656 ft] (1.25 mm
2
[AWG16] or more)
• Remote controller cable length: m
1
, m
1
+m
2
+m
3
and
m
1
+m
2
+m
3
+m
4
200 m [656 ft] (0.3 to 1.25 mm
2
[AWG20 to
AWG16])
en
RG79F368H02_EN.indd 11
2019/11/18 15:57:14
012