5
3. Installing the outdoor unit
• Be sure to install the unit in a sturdy, level surface to prevent rattling noises during
operation. (Fig. 3-1)
<Foundation specifications>
Foundation bolt
M10 (3/8")
Thickness of concrete
120 mm (4-23/32")
Length of bolt
70 mm (2-3/4")
Weight-bearing capacity
320 kg (705 lbs)
• Make sure that the length of the foundation bolt is within 30 mm (1-3/16") of the
bottom surface of the base.
• Secure the base of the unit firmly with four-M10 foundation bolts in sturdy loca-
tions.
Installing the outdoor unit
• Do not block the vent. If the vent is blocked, operation will be hindered and break-
down may result.
• In addition to the unit base, use the installation holes on the back of the unit to
attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 ×
15 mm, ø13/16" × 19/32" or less) and install on site.
Warning:
• The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.
Caution:
• Install the unit on a rigid structure to prevent excessive operation sound or
vibration.
4. Installing the refrigerant piping
4.1. Precautions for devices that use R410A refrigerant
• Refer to page 2 for precautions not included below on using air conditioners with
R410A refrigerant.
• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil ap-
plied to the flared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to con-
nect the refrigerant pipes. Use refrigerant pipes with the thicknesses specified in the
table to the below. Make sure the insides of the pipes are clean and do not contain
any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust.
Warning:
When installing or relocating, or servicing the outdoor unit, use only the speci-
fied refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any
other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pres-
sure in the refrigerant line, and may result in an explosion and other hazards.
The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
ø6.35 mm (1/4 inch), ø9.52 mm (3/8 inch),
ø12.7 mm (1/2 inch)
Thickness 0.8 mm (1/32 inch)
ø15.88 mm (5/8 inch), ø19.05 mm (3/4 inch)
Thickness 1.0 mm (5/128 inch)
• Do not use pipes thinner than those specified above.
• The thicknesses listed in the table above are based on Japanese stand-
ards. Use pipes with a maximum working pressure of 4.15 MPa [601 PSIG]
or higher according to local standards.
Fig. 3-1
B
(inch)
A
M10 (3/8") bolt
B
Base
C
As long as possible
D
Vent
E
Set deep in the ground
C
E
D
A
Min. 18-11/16
Min. 1
Max. 1-3/16
23-5/8
23-5/8
8-7/8
8-7/8
13
14-9/16
63/64
41-11/32
en
RG79F368H02_EN.indd 5
2019/11/18 15:57:12
006