background image

10

6.1. Caution

1

  Follow ordinance of your governmental organization for technical standard 

related to electrical equipment, wiring regulations and guidance of each electric 

power company.

2

  Wiring for control (hereinafter referred to as transmission line) shall be (5 cm 

[2 inch] or more) apart from power source wiring so that it is not influenced by 

electric noise from power source wiring. (Do not insert transmission line and 

power source wire in the same conduit.)

3

  Be sure to provide designated grounding work to outdoor unit.

4

  Give some allowance to wiring for electrical part box of indoor and outdoor 

units, because the box is sometimes removed at the time of service work.

5

  Never connect the main power source to terminal block of transmission line. If 

connected, electrical parts will be burnt out.

6

  Use 2-core shield cable for transmission line. If transmission lines of different 

systems are wired with the same multiplecore cable, the resultant poor trans-

mitting and receiving will cause erroneous operations.

7

  Only the transmission line specified should be connected to the terminal block 

for outdoor unit transmission.

 

(Transmission line to be connected with indoor unit : Terminal block TB3 for 

transmission line, Other : Terminal block TB7 for centralized control)

 

Erroneous connection does not allow the system to operate.

8

  In case to connect with the upper class controller or to conduct group operation 

in different refrigerant systems, the control line for transmission is required 

between the outdoor units each other.

 

Connect this control line between the terminal blocks for centralized control. 

(2-wire line with no polarity)

 

When conducting group operation in different refrigerant systems without con-

necting to the upper class controller, replace the insertion of the short circuit 

connector from CN41 of one outdoor unit to CN40.

9

  Before turning outdoor unit on, be sure to turn the indoor units on.

6. Electrical work

6.3. Wiring transmission cables

1

 

Types of control cables

1.  Wiring transmission cables

Kind of transmission cable

Shielding wire (2-core) CVVS, CPEVS or MVVS

Cable diameter 

More than 1.25 mm

[AWG 16]

Maximum wiring length

Within 200 m

 

[656 ft] 

2.  M-NET Remote control cables

Kind of remote control cable Shielding wire (2-core) CVVS, CPEVS or MVVS

Cable diameter 

0.5 to 1.25 mm

[AWG 20 to AWG 16]

Remarks 

When the wiring length exceeds 10 m [32 ft], use 

cable with the same specifications as transmis-

sion line wiring.

M1

S

M2

B

A

C

M1

S

M2

TB3

TB1

TB7

D

L1 L2 GR

6.2. Control box and connecting position of wiring

 

(Fig. 6-1)

1.  Connect the wiring between the outdoor unit and the indoor unit to the trans-

mission terminal block (TB3) of the outdoor unit.

 

Connect the wiring between the outdoor unit and the centralized control system 

to the transmission terminal block (TB7) of the outdoor unit.

 

When using shielded wiring, connect the ground of the shielded wiring to the 

shield terminal (S) of the terminal block (TB3) or (TB7).

 

If the connection of the outdoor unit’s transmission power supply connector 

has been changed from CN41 to CN42, connect the shield terminal (S) of the 

terminal block (TB7) to the screw (

D

) using the included lead wire.

  *  The shield (S) terminal of the transmission terminal block (TB3) is connected to 

the ground (

C

) when the unit is shipped from the factory.

2.  Conduit mounting plates are being provided. Remove the knock-out pieces 

from the piping cover, pass the power supply and transmission wires through 

the appropriate knock-out holes, and connect the wires to the terminal block.

3.  Fix power source wiring to terminal box by using buffer bushing for tensile force 

(PG connection or the like).

Fig. 6-1

3.  MA Remote control cables

Kind of remote control cable

Sheathed 2-core cable (unshielded) CVV

Cable diameter

0.3 to 1.25 mm

[AWG 22 to AWG 16] (0.75 

to 1.25 mm

[AWG 18 to AWG 16])*

Remarks 

Within 200 m [656 ft]

*  Connected with simple remote controller.

2

 

Wiring examples

•  Controller name, symbol and allowable number of controllers.

Name

Symbol

Allowable number of controllers

Outdoor unit controller

OC

Indoor unit controller

IC

PUMY-P36NKMU3

1 to 11 units per 1 OC

PUMY-HP36NKMU1
PUMY-P48NKMU3

1 to 12 units per 1 OC

PUMY-HP48NKMU1
PUMY-P60NKMU3

Remote controller

RC

MA

Maximum of 2 per group

CONDUIT PLATE: 
accessory

ø24 knock-out hole
(For transmission wires)

ø37 knock-out hole
(For power supply wires)

 CONDUIT WASHER: 

accessory

Example of a group operation system with multiple outdoor units (Shielding wires and address setting are necessary.)

<Examples of Transmission Cable Wiring>

 

M-NET Remote Controller (Fig. 6-2)

 

MA Remote Controller (Fig. 6-3)

<Wiring Method and Address Settings>

a.  Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.

b.  Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2 

and terminal S on the transmission cable block of the indoor unit (IC).

c.  Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the 

terminal block on the remote controller (RC).

d.  Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).

e.  The jumper connector CN41 on the control panel does not change.

f.  Connect the terminal S on the terminal block for central control  for the power supply unit  to the ground terminal (

) in the electrical component box.

g.  Set the address setting switch as follows.

Unit

Range

Setting Method

IC (Main)

01 to 50

Use the most recent address within the same group of  indoor units

IC (Sub)

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be in 

sequence with the IC (Main)

OC

51 to 100

Use the most recent address of all the indoor units plus 50

*  The address automatically becomes “100” if it is set as “01 - 50”.

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

h.  The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.

C

  Screw on the electrical component box for ground connection (TB3)

D

  Screw on the electrical component box for ground connection (TB7)

A

  Power source

B

  Transmission line

en

RG79F368H02_EN.indd   10

2019/11/18   15:57:14

011

Содержание PUMY-HP36NKMU1

Страница 1: ...ccident et vous assurer d une utilisation correcte MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado Français Español English Air Conditioners OUTDOOR UNIT PUMY P36 48 60NKMU3 BS PUMY HP36 48NKMU1 Français Español English Français Español English HFC utilized R410A FOR INSTALLER POUR L INSTALLATEUR PARA...

Страница 2: ...or unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pres sure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will...

Страница 3: ...pipes that carried R22 refrigerant Replace the existing flare nuts and flare the flared sections again Do not use thin pipes Refer to page 5 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave elbow joints etc in their packaging If dust debris or moisture enters the refrigerant lines oil dete rioration or compressor breakdow...

Страница 4: ...outdoor unit Number of units that can be connected Capacity range of connected units PUMY P36NKMU3 36 kBtu h 1 11 units 18 46 8 kBtu h PUMY HP36NKMU1 PUMY P48NKMU3 48 kBtu h 1 12 units 24 62 4 kBtu h PUMY HP48NKMU1 PUMY P60NKMU3 60 kBtu h 1 12 units 30 78 0 kBtu h Table 2 Rated capacity cooling of the indoor units Indoor unit type P04 P05 P06 P08 P12 P15 P18 P24 P30 P36 P48 P54 P72 Rated capacity ...

Страница 5: ...tional air outlet guides for upward airflow 2 5 3 When installing multiple outdoor units Leave 1 25 mm space or more between the units 1 Obstacles at rear Fig 2 11 2 Obstacles at rear and above Fig 2 12 No more than 3 units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front Fig 2 13 When using the op...

Страница 6: ... with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil ap plied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to con nect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful conta...

Страница 7: ...thickness Excessive thickness may cause incorrect installation of the indoor unit and lack of thickness may cause dew drippage Warning When pumping down the refrigerant stop the compressor before disconnect ing the refrigerant pipes The compressor may burst and cause injury if any foreign substance such as air enters the system A Outdoor Unit B First Branch C Indoor unit D Cap A Outdoor Unit B Fir...

Страница 8: ...ssor Abnormal noise or vibration may result 1Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil Ap plied on site When usual pipe sealing is used refer to Table 2 for flaring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements ...

Страница 9: ...otectively wrapped up to a diameter of ø90 mm 3 9 16 before or after connecting the pipes Cut out the knockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Note Triple Evacuatio...

Страница 10: ...52 Total capacity of connected indoor units Amount for the indoor units P36 48 HP36 48 m 19 0 g m ft 0 21 oz ft P36 48 HP36 48 m 50 0 g m ft 0 55 oz ft 27 1 5 kg 53 oz 28 54 2 5 kg 88 oz P60 m 27 0 g m ft 0 29 oz ft P60 m 70 0 g m ft 0 75 oz ft 55 3 0 kg 106 oz Included refrigerant amount when shipped from the factory Included refrigerant amount P36 48 HP36 48 4 8 kg 169 oz P60 5 1 kg 180 oz 4 7 A...

Страница 11: ...nsmission terminal block TB3 is connected to the ground C when the unit is shipped from the factory 2 Conduit mounting plates are being provided Remove the knock out pieces from the piping cover pass the power supply and transmission wires through the appropriate knock out holes and connect the wires to the terminal block 3 Fix power source wiring to terminal box by using buffer bushing for tensil...

Страница 12: ...4 A P60 8 4 AWG8 8 4 AWG8 3 4 inch 40 A 40 A 30 mA 0 1 sec or less 36 A 45 A Indoor Unit Refer to installation manual of indoor unit 1 Please follow applicable federal state or local codes to prevent potential leakage electric shock Or install a ground fault interrupt for the prevention of leakage and electric shock IMPORTANT If a current leakage breaker is used it should be compatible with higher...

Страница 13: ...xternal force is imparted to terminal connections If connections are not fixed firmly it may cause heating or fire Be sure to use the appropriate type of overcurrent protection switch Note that generated overcurrent may include some amount of direct current Turn on main power when the ambient temperature is 20 C 4 F or higher In below 20 C 4 F it needs at least 12hr stand by before the units opera...

Страница 14: ...ops due to accumulation of refrigerant in the compressor The resistance will rise above 1 MΩ after the compressor is warmed up for 12 hours The time necessary to warm up the compressor varies according to atmos pheric conditions and refrigerant accumulation To operate the compressor with refrigerant accumulated in the compressor the compressor must be warmed up at least 12 hours to prevent breakdo...

Страница 15: ...lected by switching the DIP switch 9 2 on outdoor controller board It is possible to set it to the following power consumption compared with ratings by setting SW1 2 Outdoor controller board DIP SW9 2 SW1 SW2 Function Silent mode OFF ON Silent mode operation Demand control ON OFF OFF 100 Normal ON OFF 75 ON ON 50 OFF ON 0 Stop A Remote control panel B Relay circuit C External input adapter PAC SC3...

Страница 16: ...produire Lors de l installation du déplacement ou de l entretien de l appareil extérieur n utilisez que le réfrigérant spécifié R410A pour remplir les tuyaux de réfrigérant Ne pas le mélanger avec un autre réfrigérant et faire le vide d air dans les tuyaux Siduréfrigérantestmélangéavecdel air celapeutprovoquerdespointesdepression dans les tuyaux de réfrigérant et entraîner une explosion et d autre...

Страница 17: ...ns suivantes en cas de réutilisation de tuyaux de réfrigérant R22 existants Remplacer les écrous évasés existants et évaser de nouveau les sections évasées Ne pas utiliser de tuyaux fins Se reporter à la page 5 Stocker à l intérieur les tuyaux à utiliser pendant l installation et couvrir les deux extrémités jusqu au processus de brasage Laisser les joints de coude etc dans leur emballage L infiltr...

Страница 18: ...ur Capacité de l appareil extérieur Nombre d appa reils pouvant être raccordés Plage de capaci tés des appareils raccordés PUMY P36NKMU3 36 kBtu h 1 11 appareils 18 46 8 kBtu h PUMY HP36NKMU1 PUMY P48NKMU3 48 kBtu h 1 12 appareils 24 62 4 kBtu h PUMY HP48NKMU1 PUMY P60NKMU3 60 kBtu h 1 12 appareils 30 78 0 kBtu h Tableau 2 Capacité nominale refroidissement des appareils intérieurs Type d appareil ...

Страница 19: ... air en option pour un débit d air vers le haut 2 5 3 Lors de l installation de plusieurs appareils extérieurs Espacer les appareils de 1 25 mm minimum 1 Obstacles à l arrière Fig 2 11 2 Obstacles à l arrière et au dessus Fig 2 12 Ne pas installer côte à côte plus de trois appareils Espacer également les appareils comme illustré Ne pas utiliser les guidages de sortie d air en option pour un débit ...

Страница 20: ...age 2 pour les consignes non reprises ci dessous concernant l utilisation de climatiseurs avec un réfrigérant R410A Appliquer une petite quantité d huile ester éther ou alkylbenzène comme huile réfrigérante sur les sections évasées Utiliser le cuivre phosphoreux C1220 pour des tuyaux sans soudure en cuivre et en alliage de cuivre pour raccorder les tuyaux de réfrigérant Utiliser les tuyaux de réfr...

Отзывы: