background image

8

4.4. Refrigerant piping (Fig. 4-5)

Remove the service panel 

D

 (three screws) and the front piping cover 

A

 (two 

screws) and rear piping cover 

B

 (two screws).

1

  Perform refrigerant piping connections for the indoor/outdoor unit when the 

outdoor unit’s stop valve is completely closed.

2

  Vacuum-purge air from the indoor unit and the connection piping.

Evacuation

Evacuate with the valve of the outdoor unit closed and evacuate both the connec-

tion piping and the indoor unit from the service port provided on the valve of the 

outdoor unit using a vacuum pump. (Always evacuate from the service port of both 

liquid pipe and gas pipe.) After the vacuum reaches 650 Pa [abs] [0.0943 psi/5 

Torr], continue evacuation for at least one hour or more. Then, stop the vacuum 

pump and leave it for 1 hour. Ensure the degree of vacuum has not increased. 

(If 

the degree of vacuum increase is larger than 130 Pa [0.01886 psi/1.0 Torr], 

water might have entered. Apply pressure to dry nitrogen gas up to 0.05 MPa 

[7.25 psi] and vacuum again.)

 Finally, seal in with the liquid refrigerant through 

the liquid pipe, and adjust the gas piping to obtain an appropriate amount of the 

refrigerant during operation.

*  Never perform air purging using refrigerant.

3

 

After connecting the refrigerant pipes, check the connected pipes and the 

indoor unit for gas leaks. (Refer to 4.5. Refrigerant pipe airtight testing method)

4

  Vacuumize the refrigerant lines through the service port of the liquid and gas 

stop valves. And then open the stop valves completely (for both the liquid and 

gas stop valves). This will completely connect the refrigerant lines of the indoor 

and outdoor units.

•  If the stop valves are left closed and the unit is operated, the compressor 

and control valves will be damaged.

•  Use a leak detector or soapy water to check for gas leaks at the pipe con-

nection sections of the outdoor unit.

•  Do not use the refrigerant from the unit to purge air from the refrigerant 

lines.

•  After the valve work is completed, tighten the valve caps to the correct 

torque: 20 to 25 N·m [14 to 18 ft·lbs] (200 to 250 kgf·cm).

  Failure to replace and tighten the caps may result in refrigerant leakage. In 

addition, do not damage the insides of the valve caps as they act as a seal 

to prevent refrigerant leakage.

5

  Use sealant to seal the ends of the thermal insulation around the pipe connec-

tion sections to prevent water from entering the thermal insulation.

Refrigerant pipes are protectively wrapped 

• The pipes can be protectively wrapped up to a diameter of ø90 mm (3-9/16") before 

or after connecting the pipes. Cut out the knockout in the pipe cover following the 

groove and wrap the pipes.

Pipe inlet gap

•  Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain.

(If the gaps are not closed, noise may be emitted or water and dust will enter the 

unit and breakdown may result.)

Note:

<Triple Evacuation>

•  Evacuate the system to 4,000 microns from both service valves. System 

manifold gauges must not be used to measure vacuum. A micron gauge 

must be used at all times.

-  Break the vacuum with Nitrogen (N2) into the discharge service valve to 0 PSIG.

•  Evacuate the system to 1,500 microns from the suction service valve. 

-  Break the vacuum with Nitrogen (N2) into the discharge service valve to 0 PSIG.

•  Evacuate the system to 500 microns. System must hold the vacuum at 500 

microns for a minimum of 1 hour. 

•  Conduct a rise test for a minimum of 30 minutes.

4.5. Refrigerant pipe airtight testing method

(1) Connect the testing tools.

•  Make sure the stop valves 

A

 

B

 are closed and do not open them.

•  Add pressure to the refrigerant lines through the service port 

C

 of the liquid 

stop valve 

A

 and the gas stop valve 

B

.

(2) Do not add pressure to the specified pressure all at once; add pressure little by 

little.

1

 Pressurize to 0.5 MPa [73 PSIG], wait five minutes, and make sure the pres-

sure does not decrease.

2

 Pressurize to 1.5 MPa [218 PSIG], wait five minutes, and make sure the 

pressure does not decrease.

3

 Pressurize to 4.15 MPa [601 PSIG] and measure the surrounding tempera-

ture and refrigerant pressure.

(3) If the specified pressure holds for about one day and does not decrease, the 

pipes have passed the test and there are no leaks.

•  If the surrounding temperature changes by 1°C [1.8°F], the pressure will 

change by about 0.01 MPa [1.5 PSIG]. Make the necessary corrections.

(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the 

source of the gas leak.

4. Installing the refrigerant piping

Fig. 4-6

Fig. 4-7

Fig. 4-8

A

 Valve body

 

F

 Completely closed

B

 Unit side

 

G

 Completely open  

C

 Service port

 

H

 Refrigerant piping side   (On-site installation) 

D

 Handle

 

I

 Direction the refrigerant flows in  

E

 Cap

 

J

 Valve stem  

C

(1)

1

2

H

B

A

E

C

F

D

G

B

C

J

I

H

E

(2)

B

C

E

A

D

Fig. 4-5

A

  Front piping cover

B

  Piping cover

C

  Stop valve

Service panel

E

  Bend radius : 100 mm - 150 mm (3-15/16″ – 5-7/8″)

A

  Stop valve <Liquid side>

B

  Stop valve <Gas side>

C

  Service port

D

  Open/Close section

E

  Local pipe

F

  Sealed, same way for gas side

G

  Pipe cover

H

  Do not use a wrench here.

  Refrigerant leakage may result.

I

  Use two wrenches here.

A

B

H

I

C

D

E
F

G

C

en

RG79F368H02_EN.indd   8

2019/11/18   15:57:13

009

Содержание PUMY-HP36NKMU1

Страница 1: ...ccident et vous assurer d une utilisation correcte MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado Français Español English Air Conditioners OUTDOOR UNIT PUMY P36 48 60NKMU3 BS PUMY HP36 48NKMU1 Français Español English Français Español English HFC utilized R410A FOR INSTALLER POUR L INSTALLATEUR PARA...

Страница 2: ...or unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pres sure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will...

Страница 3: ...pipes that carried R22 refrigerant Replace the existing flare nuts and flare the flared sections again Do not use thin pipes Refer to page 5 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave elbow joints etc in their packaging If dust debris or moisture enters the refrigerant lines oil dete rioration or compressor breakdow...

Страница 4: ...outdoor unit Number of units that can be connected Capacity range of connected units PUMY P36NKMU3 36 kBtu h 1 11 units 18 46 8 kBtu h PUMY HP36NKMU1 PUMY P48NKMU3 48 kBtu h 1 12 units 24 62 4 kBtu h PUMY HP48NKMU1 PUMY P60NKMU3 60 kBtu h 1 12 units 30 78 0 kBtu h Table 2 Rated capacity cooling of the indoor units Indoor unit type P04 P05 P06 P08 P12 P15 P18 P24 P30 P36 P48 P54 P72 Rated capacity ...

Страница 5: ...tional air outlet guides for upward airflow 2 5 3 When installing multiple outdoor units Leave 1 25 mm space or more between the units 1 Obstacles at rear Fig 2 11 2 Obstacles at rear and above Fig 2 12 No more than 3 units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front Fig 2 13 When using the op...

Страница 6: ... with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil ap plied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to con nect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful conta...

Страница 7: ...thickness Excessive thickness may cause incorrect installation of the indoor unit and lack of thickness may cause dew drippage Warning When pumping down the refrigerant stop the compressor before disconnect ing the refrigerant pipes The compressor may burst and cause injury if any foreign substance such as air enters the system A Outdoor Unit B First Branch C Indoor unit D Cap A Outdoor Unit B Fir...

Страница 8: ...ssor Abnormal noise or vibration may result 1Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil Ap plied on site When usual pipe sealing is used refer to Table 2 for flaring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements ...

Страница 9: ...otectively wrapped up to a diameter of ø90 mm 3 9 16 before or after connecting the pipes Cut out the knockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Note Triple Evacuatio...

Страница 10: ...52 Total capacity of connected indoor units Amount for the indoor units P36 48 HP36 48 m 19 0 g m ft 0 21 oz ft P36 48 HP36 48 m 50 0 g m ft 0 55 oz ft 27 1 5 kg 53 oz 28 54 2 5 kg 88 oz P60 m 27 0 g m ft 0 29 oz ft P60 m 70 0 g m ft 0 75 oz ft 55 3 0 kg 106 oz Included refrigerant amount when shipped from the factory Included refrigerant amount P36 48 HP36 48 4 8 kg 169 oz P60 5 1 kg 180 oz 4 7 A...

Страница 11: ...nsmission terminal block TB3 is connected to the ground C when the unit is shipped from the factory 2 Conduit mounting plates are being provided Remove the knock out pieces from the piping cover pass the power supply and transmission wires through the appropriate knock out holes and connect the wires to the terminal block 3 Fix power source wiring to terminal box by using buffer bushing for tensil...

Страница 12: ...4 A P60 8 4 AWG8 8 4 AWG8 3 4 inch 40 A 40 A 30 mA 0 1 sec or less 36 A 45 A Indoor Unit Refer to installation manual of indoor unit 1 Please follow applicable federal state or local codes to prevent potential leakage electric shock Or install a ground fault interrupt for the prevention of leakage and electric shock IMPORTANT If a current leakage breaker is used it should be compatible with higher...

Страница 13: ...xternal force is imparted to terminal connections If connections are not fixed firmly it may cause heating or fire Be sure to use the appropriate type of overcurrent protection switch Note that generated overcurrent may include some amount of direct current Turn on main power when the ambient temperature is 20 C 4 F or higher In below 20 C 4 F it needs at least 12hr stand by before the units opera...

Страница 14: ...ops due to accumulation of refrigerant in the compressor The resistance will rise above 1 MΩ after the compressor is warmed up for 12 hours The time necessary to warm up the compressor varies according to atmos pheric conditions and refrigerant accumulation To operate the compressor with refrigerant accumulated in the compressor the compressor must be warmed up at least 12 hours to prevent breakdo...

Страница 15: ...lected by switching the DIP switch 9 2 on outdoor controller board It is possible to set it to the following power consumption compared with ratings by setting SW1 2 Outdoor controller board DIP SW9 2 SW1 SW2 Function Silent mode OFF ON Silent mode operation Demand control ON OFF OFF 100 Normal ON OFF 75 ON ON 50 OFF ON 0 Stop A Remote control panel B Relay circuit C External input adapter PAC SC3...

Страница 16: ...produire Lors de l installation du déplacement ou de l entretien de l appareil extérieur n utilisez que le réfrigérant spécifié R410A pour remplir les tuyaux de réfrigérant Ne pas le mélanger avec un autre réfrigérant et faire le vide d air dans les tuyaux Siduréfrigérantestmélangéavecdel air celapeutprovoquerdespointesdepression dans les tuyaux de réfrigérant et entraîner une explosion et d autre...

Страница 17: ...ns suivantes en cas de réutilisation de tuyaux de réfrigérant R22 existants Remplacer les écrous évasés existants et évaser de nouveau les sections évasées Ne pas utiliser de tuyaux fins Se reporter à la page 5 Stocker à l intérieur les tuyaux à utiliser pendant l installation et couvrir les deux extrémités jusqu au processus de brasage Laisser les joints de coude etc dans leur emballage L infiltr...

Страница 18: ...ur Capacité de l appareil extérieur Nombre d appa reils pouvant être raccordés Plage de capaci tés des appareils raccordés PUMY P36NKMU3 36 kBtu h 1 11 appareils 18 46 8 kBtu h PUMY HP36NKMU1 PUMY P48NKMU3 48 kBtu h 1 12 appareils 24 62 4 kBtu h PUMY HP48NKMU1 PUMY P60NKMU3 60 kBtu h 1 12 appareils 30 78 0 kBtu h Tableau 2 Capacité nominale refroidissement des appareils intérieurs Type d appareil ...

Страница 19: ... air en option pour un débit d air vers le haut 2 5 3 Lors de l installation de plusieurs appareils extérieurs Espacer les appareils de 1 25 mm minimum 1 Obstacles à l arrière Fig 2 11 2 Obstacles à l arrière et au dessus Fig 2 12 Ne pas installer côte à côte plus de trois appareils Espacer également les appareils comme illustré Ne pas utiliser les guidages de sortie d air en option pour un débit ...

Страница 20: ...age 2 pour les consignes non reprises ci dessous concernant l utilisation de climatiseurs avec un réfrigérant R410A Appliquer une petite quantité d huile ester éther ou alkylbenzène comme huile réfrigérante sur les sections évasées Utiliser le cuivre phosphoreux C1220 pour des tuyaux sans soudure en cuivre et en alliage de cuivre pour raccorder les tuyaux de réfrigérant Utiliser les tuyaux de réfr...

Отзывы: