background image

1

Contents

1. Safety precautions

  Before installing the unit, make sure you read all the “Safety precautions”.

  Please report to or take consent by the supply authority before connec-

tion to the system.

After installation work has been completed, explain the “Safety Precautions” use, 

and maintenance of the unit to the customer according to the information in the 

Operation Manual and perform the test run to ensure normal operation. Both the 

Installation Manual and Operation Manual must be given to the user for keeping. 

These manuals must be passed on to subsequent users.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

•  The unit must not be installed by the user. Ask a dealer or an authorized 

technician to install the unit. If the unit is installed incorrectly, water leakage, 

electric shock, or fire may result.

•  For installation work, follow the instructions in the Installation Manual and use 

tools and pipe components specifically made for use with R410A refrigerant.

•  The R410A refrigerant in the HFC system is pressurized 1.6 times the pres-

sure of usual refrigerants. If pipe components not designed for R410A refrig-

erant are used and the unit is not installed correctly, the pipes may burst and 

cause damage or injuries. In addition, water leakage, electric shock, or fire 

may result.

•  When installing the unit, use appropriate protective equipment and tools for 

safety. Failure to do so could cause injuries.

•  The unit must be installed according to the instructions in order to minimize 

the risk of damage from earthquakes, typhoons, or strong winds. An incor-

rectly installed unit may fall down and cause damage or injuries.

•  The unit must be securely installed on a structure that can sustain its weight.

If the unit is mounted on an unstable structure, it may fall down and cause 

damage or injuries.

•  If the air conditioner is installed in a small room, measures must be taken to 

prevent the refrigerant concentration in the room from exceeding the safety limit 

in the event of refrigerant leakage. Consult a dealer regarding the appropriate 

measures to prevent the allowable concentration from being exceeded.

Should the refrigerant leak and cause the concentration limit to be exceeded, 

hazards due to lack of oxygen in the room may result.

•  Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a flame, poisonous gases will be released.

•  All electric work must be performed by a qualified technician according to 

local regulations and the instructions given in this manual. The units must 

be powered by dedicated power lines and the correct voltage and circuit 

breakers must be used. Power lines with insufficient capacity or incorrect 

electrical work may result in electric shock or fire.

•  Be sure to connect the power supply cords and the connecting wires for the 

indoor units and outdoor units directly to the units (no intermediate connec-

tions).

Intermediate connections can lead to communication errors if water enters 

the cords or wires and causes insufficient insulation to ground or a poor 

electrical contact at the intermediate connection point.

(If an intermediate connection is necessary, be sure to take measures to 

prevent water from entering the cords and wires.)

•  Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, 

to connect the refrigerant pipes. If the pipes are not connected correctly, the 

unit will not be properly grounded and electric shock may result.

•  Use only specified cables for wiring. The wiring connections must be made 

securely with no tension applied on the terminal connections. Also, never 

splice the cables for wiring (unless otherwise indicated in this document). 

Failure to observe these instructions may result in overheating or a fire.

•  The terminal block cover panel of the outdoor unit must be firmly attached. If 

the cover panel is mounted incorrectly and dust and moisture enter the unit, 

electric shock or fire may result.

•  When installing or relocating, or servicing the outdoor unit, use only the 

specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it 

with any other refrigerant and do not allow air to remain in the lines.

If air is mixed with the refrigerant, then it can be the cause of abnormal high pres-

sure in the refrigerant line, and may result in an explosion and other hazards.

The use of any refrigerant other than that specified for the system will cause 

mechanical failure or system malfunction or unit breakdown. In the worst 

case, this could lead to a serious impediment to securing product safety.

•  Use only  authorized accessories and ask a dealer or an authorized techni-

cian to install them. If accessories are incorrectly installed, water leakage, 

electric shock, or fire may result.

•  Do not alter the unit. It may cause fire, electric shock, injury or water leakage.

•  The user should never attempt to repair the unit or transfer it to another location.

If the unit is installed incorrectly, water leakage, electric shock, or fire may 

result. If the air conditioner must be repaired or moved, ask a dealer or an 

authorized technician.

•  After installation has been completed, check for refrigerant leaks. If refriger-

ant leaks into the room and comes into contact with the flame of a heater or 

portable cooking range, poisonous gases will be released.

•  When opening or closing the valve below freezing temperatures, refrigerant 

may spurt out from the gap between the valve stem and the valve body, 

resulting in injuries.

1.1. Before installation 

 Caution:

•  Do not use the unit in an unusual environment. If the air conditioner is 

installed in areas exposed to steam, volatile oil (including machine oil), or 

sulfuric gas, areas exposed to high salt content such as the seaside, or areas 

where the unit will be covered by snow, the performance can be significantly 

reduced and the internal parts can be damaged.

• Do not install the unit where combustible gases may leak, be produced, 

flow, or accumulate. If combustible gas accumulates around the unit, fire or 

explosion may result.

 Warning:

Describes precautions that must be observed to prevent danger of injury or 

death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

• The outdoor unit produces condensation during the heating operation. Make 

sure to provide drainage around the outdoor unit if such condensation is 

likely to cause damage.

• When installing the unit in a hospital or communications office, be prepared 

for noise and electronic interference. Inverters, home appliances, high-

frequency medical equipment, and radio communications equipment can 

cause the air conditioner to malfunction or breakdown. The air conditioner 

may also affect medical equipment, disturbing medical care, and communi-

cations equipment, harming the screen display quality.

1.2. Before installation (relocation) 

 Caution:

•  Be  extremely  careful  when  transporting  the  units.  2  or  more  persons  are 

needed to handle the unit, as it weighs 20 kg, 44 lbs or more. Do not grasp 

the packaging bands. Wear protective gloves to remove the unit from the 

packaging and to move it, as you can injure your hands on the fins or the 

edge of other parts.

•  Be sure to safely dispose of the packaging materials. Packaging materials, 

such as nails and other metal or wooden parts may cause stabs or other 

injuries.

• The base and attachments of the outdoor unit must be periodically checked 

for looseness, cracks or other damage. If such defects are left uncorrected, 

the unit may fall down and cause damage or injuries.

• Do not clean the air conditioner unit with water. Electric shock may result.

• Tighten all flare nuts to specification using a torque wrench. If tightened too 

much, the flare nut can break after an extended period and refrigerant can 

leak out.

Confirmation of parts attached

In addition to this manual, the following part is supplied with the outdoor unit.

It is used for grounding the S terminal of transmission terminal block TB7. 

For detail refers to “6. Electrical work”.

Grounding lead wire

1. Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2. Installation location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3. Installing the outdoor unit   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4. Installing the refrigerant piping   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

5. Drainage piping work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

6. Electrical work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

7. Test run  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

8. Special Functions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

en

RG79F368H02_EN.indd   1

2019/11/18   15:57:10

002

Содержание PUMY-HP36NKMU1

Страница 1: ...ccident et vous assurer d une utilisation correcte MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado Français Español English Air Conditioners OUTDOOR UNIT PUMY P36 48 60NKMU3 BS PUMY HP36 48NKMU1 Français Español English Français Español English HFC utilized R410A FOR INSTALLER POUR L INSTALLATEUR PARA...

Страница 2: ...or unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pres sure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will...

Страница 3: ...pipes that carried R22 refrigerant Replace the existing flare nuts and flare the flared sections again Do not use thin pipes Refer to page 5 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave elbow joints etc in their packaging If dust debris or moisture enters the refrigerant lines oil dete rioration or compressor breakdow...

Страница 4: ...outdoor unit Number of units that can be connected Capacity range of connected units PUMY P36NKMU3 36 kBtu h 1 11 units 18 46 8 kBtu h PUMY HP36NKMU1 PUMY P48NKMU3 48 kBtu h 1 12 units 24 62 4 kBtu h PUMY HP48NKMU1 PUMY P60NKMU3 60 kBtu h 1 12 units 30 78 0 kBtu h Table 2 Rated capacity cooling of the indoor units Indoor unit type P04 P05 P06 P08 P12 P15 P18 P24 P30 P36 P48 P54 P72 Rated capacity ...

Страница 5: ...tional air outlet guides for upward airflow 2 5 3 When installing multiple outdoor units Leave 1 25 mm space or more between the units 1 Obstacles at rear Fig 2 11 2 Obstacles at rear and above Fig 2 12 No more than 3 units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front Fig 2 13 When using the op...

Страница 6: ... with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil ap plied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to con nect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful conta...

Страница 7: ...thickness Excessive thickness may cause incorrect installation of the indoor unit and lack of thickness may cause dew drippage Warning When pumping down the refrigerant stop the compressor before disconnect ing the refrigerant pipes The compressor may burst and cause injury if any foreign substance such as air enters the system A Outdoor Unit B First Branch C Indoor unit D Cap A Outdoor Unit B Fir...

Страница 8: ...ssor Abnormal noise or vibration may result 1Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil Ap plied on site When usual pipe sealing is used refer to Table 2 for flaring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements ...

Страница 9: ...otectively wrapped up to a diameter of ø90 mm 3 9 16 before or after connecting the pipes Cut out the knockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Note Triple Evacuatio...

Страница 10: ...52 Total capacity of connected indoor units Amount for the indoor units P36 48 HP36 48 m 19 0 g m ft 0 21 oz ft P36 48 HP36 48 m 50 0 g m ft 0 55 oz ft 27 1 5 kg 53 oz 28 54 2 5 kg 88 oz P60 m 27 0 g m ft 0 29 oz ft P60 m 70 0 g m ft 0 75 oz ft 55 3 0 kg 106 oz Included refrigerant amount when shipped from the factory Included refrigerant amount P36 48 HP36 48 4 8 kg 169 oz P60 5 1 kg 180 oz 4 7 A...

Страница 11: ...nsmission terminal block TB3 is connected to the ground C when the unit is shipped from the factory 2 Conduit mounting plates are being provided Remove the knock out pieces from the piping cover pass the power supply and transmission wires through the appropriate knock out holes and connect the wires to the terminal block 3 Fix power source wiring to terminal box by using buffer bushing for tensil...

Страница 12: ...4 A P60 8 4 AWG8 8 4 AWG8 3 4 inch 40 A 40 A 30 mA 0 1 sec or less 36 A 45 A Indoor Unit Refer to installation manual of indoor unit 1 Please follow applicable federal state or local codes to prevent potential leakage electric shock Or install a ground fault interrupt for the prevention of leakage and electric shock IMPORTANT If a current leakage breaker is used it should be compatible with higher...

Страница 13: ...xternal force is imparted to terminal connections If connections are not fixed firmly it may cause heating or fire Be sure to use the appropriate type of overcurrent protection switch Note that generated overcurrent may include some amount of direct current Turn on main power when the ambient temperature is 20 C 4 F or higher In below 20 C 4 F it needs at least 12hr stand by before the units opera...

Страница 14: ...ops due to accumulation of refrigerant in the compressor The resistance will rise above 1 MΩ after the compressor is warmed up for 12 hours The time necessary to warm up the compressor varies according to atmos pheric conditions and refrigerant accumulation To operate the compressor with refrigerant accumulated in the compressor the compressor must be warmed up at least 12 hours to prevent breakdo...

Страница 15: ...lected by switching the DIP switch 9 2 on outdoor controller board It is possible to set it to the following power consumption compared with ratings by setting SW1 2 Outdoor controller board DIP SW9 2 SW1 SW2 Function Silent mode OFF ON Silent mode operation Demand control ON OFF OFF 100 Normal ON OFF 75 ON ON 50 OFF ON 0 Stop A Remote control panel B Relay circuit C External input adapter PAC SC3...

Страница 16: ...produire Lors de l installation du déplacement ou de l entretien de l appareil extérieur n utilisez que le réfrigérant spécifié R410A pour remplir les tuyaux de réfrigérant Ne pas le mélanger avec un autre réfrigérant et faire le vide d air dans les tuyaux Siduréfrigérantestmélangéavecdel air celapeutprovoquerdespointesdepression dans les tuyaux de réfrigérant et entraîner une explosion et d autre...

Страница 17: ...ns suivantes en cas de réutilisation de tuyaux de réfrigérant R22 existants Remplacer les écrous évasés existants et évaser de nouveau les sections évasées Ne pas utiliser de tuyaux fins Se reporter à la page 5 Stocker à l intérieur les tuyaux à utiliser pendant l installation et couvrir les deux extrémités jusqu au processus de brasage Laisser les joints de coude etc dans leur emballage L infiltr...

Страница 18: ...ur Capacité de l appareil extérieur Nombre d appa reils pouvant être raccordés Plage de capaci tés des appareils raccordés PUMY P36NKMU3 36 kBtu h 1 11 appareils 18 46 8 kBtu h PUMY HP36NKMU1 PUMY P48NKMU3 48 kBtu h 1 12 appareils 24 62 4 kBtu h PUMY HP48NKMU1 PUMY P60NKMU3 60 kBtu h 1 12 appareils 30 78 0 kBtu h Tableau 2 Capacité nominale refroidissement des appareils intérieurs Type d appareil ...

Страница 19: ... air en option pour un débit d air vers le haut 2 5 3 Lors de l installation de plusieurs appareils extérieurs Espacer les appareils de 1 25 mm minimum 1 Obstacles à l arrière Fig 2 11 2 Obstacles à l arrière et au dessus Fig 2 12 Ne pas installer côte à côte plus de trois appareils Espacer également les appareils comme illustré Ne pas utiliser les guidages de sortie d air en option pour un débit ...

Страница 20: ...age 2 pour les consignes non reprises ci dessous concernant l utilisation de climatiseurs avec un réfrigérant R410A Appliquer une petite quantité d huile ester éther ou alkylbenzène comme huile réfrigérante sur les sections évasées Utiliser le cuivre phosphoreux C1220 pour des tuyaux sans soudure en cuivre et en alliage de cuivre pour raccorder les tuyaux de réfrigérant Utiliser les tuyaux de réfr...

Отзывы: