80
1
2
3
4
5
BRN
RED
ORN
YLW
GRN
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
E N G A G E D
G R O U P
A C T I V E B Y P A S S
G R O U P
S E L E C T I O N
P R O G R A M
T I M E R
C O N T R O L L E R
O P E R A T I O N
D U A L C E N T R A L
1 2 3 4 5 6 7 8 9 10
1 1 7
117
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
E N G A G E D
G R O U P
A C T I V E B Y P A S S
G R O U P
S E L E C T I O N
P R O G R A M
T I M E R
C O N T R O L L E R
O P E R A T I O N
D U A L C E N T R A L
1 2 3 4 5 6 7 8 9 10
1 1 3
113
1 2
10 9 8 7 6 5 4 3 2 1
5 6 . 5
1 1
2 3 . 5
8
BACK
ACTIVE
BYPASS
POWER
ON/OFF
DUAL
CENTRAL
AHEAD
MITSUBISHI ELECTRIC
E N G A G E D
G R O U P
A C T I V E B Y P A S S
G R O U P
S E L E C T I O N
P R O G R A M
T I M E R
C O N T R O L L E R
O P E R A T I O N
D U A L C E N T R A L
1 2 3 4 5 6 7 8 9 10
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check). Adapter connection is described on page 81.
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC-
825AD)is also needed. See page 81.
Part No.
PAC-SA88HA-E
Part No.
PAC-805RC
5-1. Dimensions
5-2. Functions
"ENGAGED" indicator
When this indicator is lit, transmission is in
progress and all switches are inoperative.
DUAL/CENTRAL switch
This change-over switch governing the
operation of the accessory remote con-
troller.
"DUAL"
Instructions from both the accessory
remote controller and the centralized
remote controller are valid. (Priority given
to the last instruction received.)
"CENTRAL"
ON/OFF switching by the accessory
remote controller is invalidated. Control is
by the centralized remote controller only.
Initial setting is "DUAL".
LCD Matrix Display
This display indicates the operational sta-
tus of all connected units either by steady
lighting or by flashing.
POWER ON/OFF switch
Operation ON/OFF switch.
▲
BACK
▼
AHEAD buttons
These buttons are used to designate
the attached unit(s). (They designate
the unit to be centrally controlled.)
●
When group “00” is designated; col-
lective ON/OFF instruction is sent to all
units.
●
When group “01”-“16“ is designated;
ON/OFF instruction is sent to the des-
ignated units only.
ACTIVE/BYPASS switch
This is a change-over switch for the
program timer.
(It selects timer operation on the pro-
gram timer.)
Use “BYPASS” when a program timer
is not connected.
“ACTIVE”
The switch tums ON/OFF operational
instructions from the program timer
automatically.
“BYPASS”
ON/OFF Operation is by the central-
ized remote controller only.
Initial setting is “BYPASS”.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the
centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”.
Unit:mm
Содержание PLH Series
Страница 2: ......