4-WAY AIR FLOW SYSTEM
11
1. Placement of the air outlets
●
For this grill, the airflow direction comes in 11 patterns for PLH-3GK(H)B
1
.UK and in 6 patterns for PLH-4~6GK(H)SB
1
.UK.
Also, by setting the dip switches (SWA and SWB)on the indoor board to the appropriate settings, you can adjust the air flow
and speed. Select the settings that are needed from those in Tables 2 and 3 according to the place where you want to install
the unit.
1) Decide on the pattern of the discharge direction. For 3-and 2-direction dischardge, adjust the width of the air outlet.
<Air outlet>
340
(fully open 450)
1 direction
(fully closed)
2-direction
(fully closed)
<Air outlet>
340
3-direction
(standard)
<Air outlet>
450
2-direction
(fully open)
<Air outlet>
340
(fully open 450)
widthwise
<Air outlet>
340
(fully open 450)
Lengthwise
1-directional
(fully closed)
<Air outlet>
1-direction
(fully closed)
Widthwise:340
Lenthwise:750
(fully closed)
Widthwise
(fully open)
Lengthwise
<Air outlet>
900
4-direction
3-direction
2-direction
Airflow direction
pattern
Adjusting the opening width
PLH-3GK(H)B
1
.UK
PLH-4~6GK(H)SB
1
.UK
Pattern 1
Pattern 4
Factory setting
One air outlet
fully closed
Pattern 6
Two air outlets fully
closed, two fully open
Pattern 1
Two air outlets
on the widthwise
side fully closed.
Factory setting
(standard)
Install the insulation
4
furnished in this kit, and
close it fully.
Factory setting(standard)
Closing one lengthwise direction
Install the insulation
4
furnished
in this kit, and close it fully.
The remaining three directions
must remain standard.
Install the insulation
4
furnished
in this kit, and close it fully.
The remaining three direction must
be fully open.
The widthwise direction
on the piping side must
remain 340 (standard).
Closing one widthwise direction
Close the two widthwise directions fully. Open the two
lengthwise directions fully.
Install the insulation
4
furnished in this kit, and close it fully.
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
<Air outlet>
Widthwise:450
Lengthwise:900
(PLH-3GK(H)B
1
.UK)
(PLH-4~6
GK(H)SB
1
.UK)
Install the insulation
4
furnished in this kit, and
close it fully.
The two sides that
sandwich the piping must
remain 340
(standard).
●
To open or close the air outlets fully, see Item 2 on the next page entitled “Adjusting the width of the air outlets
(opening or closing fully)”.
2) According to the number of air outlets and the height of the ceiling to install the unit, be sure to set the dip switches on the
indoor controller board to the appropriate settings.
●
Correspondence of ceiling heights to
numbers of air outlets.
Standard
4-directional
2.7m
3.0m
3.5m
3-directional
3.0m
3.3m
3.5m
2-directional
3.5m
3.8m
3.8m
High ceiling
1
High ceiling
2
SWB
SWA