![Mitsubishi Electric PLH Series Скачать руководство пользователя страница 66](http://html.mh-extra.com/html/mitsubishi-electric/plh-series/plh-series_technical-and-service-manual_1811126066.webp)
66
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
5. Removing the heater
(Only PLH-3GK(H)B
1
, 4GK(H)SB
1
,
PLH-5GK(H)SB
1
, 6GK(H)SB
1
)
(1) Remove the fan guard.
(2) Remove the turbo fan nut and the turbo fan.
(3) Remove the 2 screws of the heater support.
(4) Pull out the heater assembly.
6. Removing the drain pump, the drain sensor, and the
indoor coil thermistor
(1) Remove the fan guard.
(2) Remove the turbo fan nut and the turbo fan.
(3) Remove the 3 screws and the electrical box.
(4) Remove the 2 screws of the service panel.
(5) Holding the knob, remove the service panel.
(6) Remove the 4 screws of the drain pump.
(7) Remove the hose connecting nut.
(8) Remove the drain pump.
(9) Remove the screw of the drain sensor holder.
(10) Remove the holder and the drain sensor.
(11) Remove the indoor coil thermistor from the holder
attached to the copper pipe.
Photo 8
Photo 7
Photo 6
4. Remove the fan motor
(1) Remove the fan guard.
(2) Remove the turbo fan nut.
(3) Pull out the turbo fan.
(4) Disconnect the connector of the fan motor lead wire.
(5) Remove the 3 nuts of the fan motor.
Photo 5
Heater support screw
Fan nut
Connector
Screws
Service
panel
Drain pump
set screws
Drain sensor
set screws
Coil
thermistor
Содержание PLH Series