![Mitsubishi Electric PLH Series Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/mitsubishi-electric/plh-series/plh-series_technical-and-service-manual_1811126057.webp)
57
3-2 Fresh air intake amount & static pressure characteristics
P(Pa)
50
-50
-100
-150
-200
0
Standard
With high efficiency filter
1
2
3
4
5
Q(m /min)
3
P(Pa)
50
-50
-100
-150
-200
0
With high
efficiency filter
1
2
3
4
5
6
7
8
9 Q(m /min)
3
With 2 intake
With 1 intake
P(Pa)
50
-50
-100
-150
-200
0
Standard
1
2
3
4
5
6
7
8
9 Q(m /min)
3
With 2 intake
With 1 intake
1
1
PLH-3GK(H)B
1
.UK (Standard / with the high efficiency filter)
2
2
PLH-4~6GK(H)SB
1
.UK (Standard)
3
3
PLH-4~6GK(H)SB
1
.UK (with the high efficiency fil-
Q
0
B
A
C
1
Curve in the
left praphs.
Duct characteristics
at site
Q
A
EC
2
Q
Qa
AD
3
Q…Planned amount of fresh air intake
A…Static pressure loss of fresh air
intake duct system with air flow
amount Q
B…Forced static pressure at air condi-
tioner inlet with air flow amount Q
C…Static pressure of booster fan with
air flow amount Q
D…Static pressure loss increase
amount of fresh air intake dust
system for air flow amount Q <Pa>
E…Static pressure of indoor unit with
air flow amount Q
Qa…Estimated amount of fresh air
intake with out D
<m
3
/min>
<Pa>
<Pa>
<Pa>
<Pa>
<Pa>
How to read curves
3-3 Interlocking operation method with duct fan
(Booster fan)
●
Whenever the indoor unit is operating, the duct fun also
operates.
(1)Connect the optional multiple remote controller
adapter(PAC-SA88HA-E)to the connector CN51 on the
indoor controller board.
(2)Drive the relay after connecting the 12V DC relay
between the Yellow and Orange connector lines.
(
w
)Use a relay under 1W.
MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
CN51
Multiple remote
controller adapter
PAC-SA88HA-E
Indoor controller board
Distance between indoor
controller board and relay
must be within 10m.
Be sure to secure insulation
material by tape and such
5
Green
Yellow
Orange
Connector (5P)
Package side
Multiplr remote
controller adapter
PAC-SA88HA-E
Be sure to secure insulation
material by tape and such
Installation at site
CN51
on
indoor unit
board
Red
Brown
1
MB
~
Содержание PLH Series