11
6. Electrical work
Function table (table 1)
Select unit number 00
Mode
Settings
Mode no.
Setting no. Initial setting
setting
Power failure automatic recovery
Not available
01
1
Available *1
2
ȅ
Indoor temperature detecting
Indoor unit operating average
02
1
ȅ
Set by indoor unit’s remote controller
2
Remote controller’s internal sensor
3
LOSSNAY connectivity
Not Supported
03
1
ȅ
Supported (indoor unit is not equipped with outdoor-air
intake)
2
Supported (indoor unit is equipped with outdoor-air intake)
3
Power voltage
9
04
1
ȅ
9
2
6HOHFWXQLWQXPEHUVWRRUDOOXQLWV$/>ZLUHGUHPRWHFRQWUROOHU@>ZLUHOHVVUHPRWHFRQWUROOHU@
Mode
Settings
Mode no.
Setting no. Initial setting
setting
Filter sign
100Hr
07
1
2500Hr
2
ȅ
1R¿OWHUVLJQLQGLFDWRU
3
Fan speed
Silent (low ceiling)
08
1
Standard
2
ȅ
High ceiling
3
No. of air outlets
4 directions
09
1
ȅ
3 directions
2
2 directions
3
,QVWDOOHGRSWLRQVKLJKHI¿FLHQF\¿OWHU
Not supported
10
1
ȅ
Supported
2
8SGRZQYDQHVHWWLQJ
Downward setting (vanes angle setup
3
)
11
1
Middle setting (vanes angle setup
1
)
2
ȅ
Draft-less setting (vanes angle setup
2
) *4
3
3D i-see Sensor positioning
Position
1
12 *3
1
Position
2
2
Position
3
(Default)
3
ȅ
3D i-see Sensor ceiling height setting
(when installing the 3D i-see Sensor panel)
Low ceiling (ceiling height: less than 2.7 m, 8.9 ft)
26
1
Standard (ceiling height: 2.7-3.5 m, 8.9-11,5 ft)
2
ȅ
High ceiling (ceiling height: 3.5-4.5 m, 11,5-14.8 ft)
3
Fan speed during the cooling thermostat is OFF
Setting fan speed
27
1
ȅ
Stop
2
Extra low
3
*1 When the power supply returns, the air conditioner will start 3 minutes or 1 minute later (hinge on Outdoor unit).
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
*3 When the 3D i-see Sensor corner panel position is changed, change this mode. Refer to page 17.
*4 Because condensation may form, do not use this setting in a high-temperature, high-humidity environment.