9-5. TROUBLESHOOTING CRITERION OF MAIN PARTS
MSZ-GS06NA MSZ-GS09NA MSZ-GS12NA MSZ-GS15NA MSZ-GS18NA MSZ-GS24NA
MSZ-GS30NA MSZ-GS36NA MSZ-GS30NA2 MSZ-GS36NA2
MSY-GS09NA MSY-GS12NA MSY-GS15NA MSY-GS18NA MSY-GS24NA MSY-GS30NA
MSY-GS36NA MSY-GS30NA2 MSY-GS36NA2
Part name
Check method and criterion
Figure
Room temperature thermistor
(RT11)
Indoor coil thermistor
(RT12 (MAIN), RT13 (SUB))
Measure the resistance with a multimeter.
Refer to 9-7. “Test point diagram and voltage”, “Indoor electronic control
P.C. board”, the chart of thermistor.
Indoor fan motor (MF)
Check 9-6. .
MSZ-GS06/09/12/15NA
MSY-GS09/12/15NA
Vane motor (MV)
Measure the resistance between the terminals with a multimeter.
(Temperature: 50 - 86°F (10 - 30°C))
Color of the lead wire
Normal
RED - BLK
223 - 268 Ω
BLK
BLK
RED
BLK BLK
ROTOR
ROTOR
MSZ-GS18/24NA
MSY-GS18/24NA
Horizontal vane motor
(MV1)
Vertical vane motor
(MV2)
Measure the resistance between the terminals with a multimeter.
(Part temperature 50 ~ 86°F)
Color of the lead wire
Normal
MSZ-GS18NA MSY-GS18NA
Horizontal vane motor (MV1)
RED-BLK
223 - 268 Ω
Vertical vane motor (MV2)
RED-YLW
219 - 273 Ω
Color of the lead wire
Normal
MSZ-GS24NA MSY-GS24NA
Horizontal vane motor (MV1)
RED-BLK
313 - 375 Ω
Vertical vane motor (MV2)
268 - 322 Ω
MSZ-GS30/36NA
MSY-GS30/36NA
MSZ-GS30/36NA2
MSY-GS30/36NA2
Horizontal vane motor
(MV1)
Vertical vane motor
(MV2, MV3)
Measure the resistance between the terminals with a multimeter.
(Part temperature 50 ~ 86°F)
Color of the lead wire
Normal
Horizontal vane motor (MV1)
RED - SKY*
240 - 260 Ω
Vertical vane motor
(MV2, MV3)
282 - 306 Ω
SKY
SKY
RED
SKY SKY
ROTOR
*SKY = SKY BLUE
YLW
YLW
RED
YLW YLW
ROTOR
ROTOR
BLU
BLU
RED
BLU BLU
ROTOR
ROTOR
MSZ-GS18NA
MSY-GS18NA
(MV1)
MSZ-GS18NA
MSY-GS18NA
(MV2)
MSZ-GS24NA
MSY-GS24NA
BLK
BLK
RED
BLK
BLK
ROTOR
ROTOR
OBH874A