3-1. OPERATING RANGE
(1) POWER SUPPLY
Rated voltage
Guaranteed voltage (V)
Indoor unit
208/230 V
1 phase
60 Hz
Min. 187
208
230
Max. 253
(2) OPERATION
Mode
Condition
Intake air temperature (°F)
DB
WB
Cooling
Standard temperature
80
67
Maximum temperature
90
73
Minimum temperature
67
57
Maximum humidity
78%
Heating
Standard temperature
70
60
Maximum temperature
80
67
Minimum temperature
70
60
3-2. OUTLET AIR SPEED AND COVERAGE RANGE
Model
Mode
Function
Airflow
(CFM)
Air speed
(ft./sec.)
Coverage
range (ft.)
MSZ-GS06NA
MSZ-GS09NA
MSY-GS09NA
MSZ-GS12NA
MSY-GS12NA
HEAT
(
MSZ
)
Dry
390
19.8
28.4
COOL
Dry
381
19.3
27.7
Wet
343
17.4
25.0
MSZ-GS15NA
MSY-GS15NA
HEAT
(
MSZ
)
Dry
437
22.2
31.7
COOL
Dry
504
25.6
36.4
Wet
454
23.0
32.9
MSZ-GS18NA
MSY-GS18NA
HEAT
(
MSZ
)
Dry
629
28.7
42.8
COOL
Dry
629
28.7
42.8
Wet
566
25.8
38.7
MSZ-GS24NA
MSY-GS24NA
HEAT
(
MSZ
)
Dry
701
17.1
35.1
COOL
Dry
701
17.1
35.1
Wet
631
15.4
31.7
MSZ-GS30NA
MSZ-GS36NA
MSY-GS30NA
MSY-GS36NA
HEAT
(
MSZ
)
Dry
803
15.1
35.3
COOL
Dry
915
17.2
40.0
Wet
823
15.4
36.1
MSZ-GS30NA2
MSZ-GS36NA2
MSY-GS30NA2
MSY-GS36NA2
HEAT
(
MSZ
)
Dry
816
15.3
35.8
COOL
Dry
932
17.5
40.8
Wet
839
15.7
36.8
● The air coverage range is the figure up
to the position where the air speed is 1
ft./sec., when air is blown out horizon-
tally from the unit properly at the High
speed position.
The coverage range should be used
only as a general guideline since it var-
ies according to the size of the room
and furniture arranged inside the room.