37
9-3. INSTRUCTION OF TROUBLESHOOTING
Indoor unit operates.
Outdoor unit does
not operate.
Indoor unit operates.
Outdoor unit does
not operate normally.
Indoor unit does not
receive the signal from
remote controller.
OPERATION INDICATOR
lamp on the indoor unit is
blinking on and off.
Outdoor unit
operates only
in Test Run
operation. *1
Outdoor unit
does not
operate even
in Test Run
operation. *1
Unit does not
operate nor-
mal operation
in COOL or
HEAT(
MSZ
)
mode.
Indoor unit
operates, when
the emergency
operation switch
is pressed.
Indoor unit does
not operate, when
the emergency
operation switch
is pressed.
Check room
temperature
thermistor.
Refer to 9-7.
“Test point
diagram and
voltage”.
Refer to “How
to check
inverter/
compressor”.
Refer to
“Check of R.V.
coil”.
Refer to 9-6.
“Check of remote
controller and
receiver P.C.
board”.
1. Check indoor/outdoor
connecting wire.
(Check if the power is
supplied to the indoor
unit.)
2. Refer to 9-6. “Check
of indoor electronic
control P.C. board and
indoor fan motor”.
Start
*1 “Test Run operation” means the operation within
30 minutes after the emergency operation switch
is pressed.
Refer to 9-4.
“TROUBLE-
SHOOTING
CHECK TABLE”.
NOTE:
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
OBH874A