8-12. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use the emergency operation switch on the front of the indoor unit.
Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote controller
run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at
High speed and the temperature control does not work.
After 30 minutes of test run operation the system shifts to EMERGENCY COOL/HEAT
(MSZ)
MODE with a set tempera-
ture of 75°F (24°C). The fan speed shifts to Med.
The coil frost prevention works even in the test run or the emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode.
Emergency operation continues until the emergency operation switch is pressed once or twice or the unit receives any
signal from the remote controller. In case of latter normal operation will start.
NOTE
: Do not press the emergency operation switch during normal operation.
Operation mode
COOL
HEAT (
MSZ
)
Set temperature
75°F(24°C)
75°F(24°C)
Fan speed
Med.
Med.
Horizontal vane
Auto
Auto
The operation mode is indicated by the
Operation Indicator lamp as follows.
MSZ
EMERGENCY
COOL
↓
EMERGENCY
HEAT
↓
STOP
MSZ
EMERGENCY
COOL
↓
EMERGENCY
HEAT
↓
STOP
MSY
EMERGENCY
COOL
↓
STOP
MSY
EMERGENCY
COOL
↓
STOP
Lit
Not lit
Operation Indicator Lamp
MSZ-GS06/09/12/15/18/24NA
MSY-GS09/12/15/18/24NA
MSZ-GS30/36NA MSZ-GS30/36NA2
MSY-GS30/36NA MSY-GS30/36NA2
8-13. 3-MINUTE TIME DELAY OPERATION
When the system turns OFF, compressor will not restart for 3 minutes as 3-minute time delay function operates to protect
compressor from overload.
8-14 . CHANGING TEMPERATURE INDICATION (°F /°C)
• The preset unit is °F.
•
°F→°C : Press RESET button while the temperature buttons are pressed.
•
°C→°F : Press RESET button or remove the batteries
.
Press RESET button gently using a fine-tipped object.