Turn OFF the power supply.
Remove indoor fan motor connector CN211
and vane motor connector CN151 from the
indoor electronic control P.C. board and turn
ON the power supply.
Does the unit operate with the remote
controller?
Does OPERATION INDICATOR lamp light
up by pressing the emergency operation
switch?
Yes
No
Measure the resistance between
CN211 and of the indoor fan motor
connector.
Measure the resistance of the horizon-
tal vane motor coil.
Refer to 9-5.
Short circuit:
Replace the indoor fan motor.
Short circuit:
Replace the horizontal vane motor and the
indoor electronic control P.C. board.
Turn OFF the power supply.
Check both “parts side” and “pattern
side” of the indoor electronic control
P.C. board visually.
Replace the indoor electronic
control P.C. board.
Are the varistor (NR11)
burnt and the fuse (F11)
blown?
No
No
Yes
Yes
Be sure to check both the fuse
and the varistor in any case.
Is the fuse (F11) blown
only?
Measure the resistance between (+)
and (-) of the indoor fan motor
connector (to CN211 on the indoor
electronic control P.C. board) . *1, *2
*1. The fan motor connector’s lead wire is red, whereas is
black.
*2. Connect “+” of the multimeter to fan motor connector’s
lead wire, and “-” to lead wire, otherwise the resis-
tance cannot be measured properly.
Yes
Is the resistance 1 MΩ
or more?
Replace the indoor electronic control
P.C. board and the indoor fan motor.
No
Replace the indoor electronic
control P.C. board
Measure the resistance of cement
resistor (R111) on the indoor elec-
tronic control P.C. board.
Yes
Is the resistance
approximately 4 Ω?
No
Replace the indoor electronic control P.C.
board and the indoor fan motor.
Replace the indoor electronic control P.C. board.
Resistor (R111)
Indoor electronic
control P.C. board
Varistor (NR11)
Fuse (F11)
CN10A
CN151
CN211
MSZ-GS30/36NA MSZ-GS30/36NA2
MSY-GS30/36NA MSY-GS30/36NA2
OBH874A