5
:
8
:
Defrost heater
ON
OFF
3. High pressure protection
In HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera-
tional frequency is controlled to prevent the condensing pressure from increasing excessively.
4. Overload starting
When the room temperature thermistor RT11 reads 18°C or more, the compressor runs with its maximum frequency regulat-
ed for 10 minutes after the start-up.
5. Defrosting
(1) Starting conditions of defrosting
When the following conditions a) ~ c) are satisfied, the defrosting starts.
a) The defrost thermistor reads -3°C or less.
b) The cumulative operation time of the compressor has reached any of the set values
w
(30, 35, 40, 45, 55, 65, 75, 85,
95, 105, 115, 125, 150 minutes).
c) More than 5 minutes have passed since the start-up of the compressor.
w
Set value of compressor operation time(hereinafter referred to as defrost interval)
This is decided by the temperature of defrost thermistor and ambient temperature thermistor, the previous defrosting
time. For example, the first defrost interval is 40 minutes long, and the second is 45 minutes long. The third and sub-
sequent intervals are set to be longer, and less frequent, depending on defrosting time.
The third and subsequent defrost intervals follow any of the three patterns …5 or 10 to 20 minutes longer, the same,
or 5 or 10 to 20 minutes shorter compared with the previous defrost interval … with the longest 150 minutes and the
shortest 30 minutes.
(2) Releasing conditions of defrosting
Defrosting is released when any of the following conditions is satisfied:
a) The defrost thermistor continues to read 5°C or more (MUZ-FA25VA) / 8°C or more (MUZ-FA25VAH) / 10°C or more
(MUZ-FA35VA) / 13°C
w
1
or 10°C
w
2
or more (MUZ-FA35VAH) for 30 seconds.
w
1 13°C (Serial No: ~6002550)
w
2 10°C (Serial No: 6002551~)
b) Defrosting time has exceeded 10 minutes.
c) Any other mode than HEAT mode is set during defrosting.
6. Defrost heater (MUZ-FA25/ FA35VAH)
(1) Starting conditions
When all of the following conditions a) ~ d) are satisfied, defrost heater turns ON to prevent ice from foaming on the
base of outdoor unit.
a) HEAT mode is selected.
b) The ambient temperature thermistor RT65 reads 5
:
or less for 5 minutes continuously. (NOTE 1).
c) The defrost thermistor RT61 reads -1
:
or less for 5 minutes continuously.
d) Outdoor fan motor is turned ON.
(2) Releasing conditions
When any of the following conditions is satisfied, defrost heater turns OFF.
a) Any other mode than HEAT mode is selected. (NOTE 2).
b) The ambient temperature thermistor RT65 reads 8
:
or more for 5 minutes continuously. (NOTE 1).
c) The defrost thermistor RT61 reads more than 15
:
for 5 minutes continuously.
d) Outdoor fan motor is turned OFF.
NOTE1 : Ambient temperature thermistor RT65.
NOTE2 : During defrosting operation defrost heater continues to be ON.