COOL and DRY operation
FAN operation
Vane angle is fixed to Angle 1.
Vane angle is fixed to Angle 4.
(4) VANE AUTO (
) mode
The microprocessor automatically determines the horizontal vane angle and operation to make the optimum room tem-
perature distribution.
(5) STOP (operation OFF) and ON-TIMER standby
When the following cases occur, the horizontal vane returns to the closed position.
(a) When OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When ON-TIMER is on standby.
(6) Dew prevention
During COOL or DRY operation at Vane Angle 4 or 5 when the compressor cumulative operation time of compressor
exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(7) SWING MODE (
)
By selecting SWING mode with VANE button, the horizontal vane swings vertically. The remote controller displays “
”.
SWING mode is cancelled when VANE button is pressed once again.
(3) Positioning
The vane presses the vane stopper once to confirm the standard position and then moves to the set angle.
Confirming of standard position is performed in case of follows.
(a) When the power supply turns ON.
(b) When the operation starts or finishes (including timer operation).
(c) When the test run starts.
(d) When the vane control is changed AUTO to MANUAL (except SWING).
(e) When the SWING is finished (including ECONO COOL).