![Mitsubishi Electric MSC-CA20VB Скачать руководство пользователя страница 126](http://html.mh-extra.com/html/mitsubishi-electric/msc-ca20vb/msc-ca20vb_service-technical-manual_1810424126.webp)
126
EMERGENCY OPERATION switch
E.O.
SW
Operation mode
COOL
HEAT
Set temperature
24
:
24
:
Fan speed
Medium
Medium
Horizontal vane
Auto
Auto
• The following indication does not depend on the
shape of lamp.
Press once <Cool>
Press again <Heat>
Press once again <Stop>
OPERATION INDICATOR lamp
Lighted
Not lighted
9-10. EMERGENCY / TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor
unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote
controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at
High speed and the system is in continuous operation (The thermostat in ON).
After 30 minutes of test run operation, the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of
24°C. The fan speed shifts to Med.
The coil frost prevention works even in emergency operation, and defrosting too.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO (
) mode.
Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any
signal from the remote controller. In case of latter, normal operation will start.
NOTE : Do not press EMERGENCY OPERATION switch during normal operation.