1. Pre-heat control is turned ON for 15 or 30 min
w
after the breaker is turned ON.
2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min.
w
and turned OFF for 30 min.
This is repeated as shown in the graph until the breaker is turned OFF.
w
When outside temperature is 20
:
or below , pre-heat control is ON for 30 min.
When outside temperature is 21
:
or above, pre-heat control is ON for 15 min.
NOTE: When the unit is started with the remote controller, pre-heat control is turned OFF.
Compressor uses 50W when pre-heat control is turned ON.
12-8. PRE-HEAT CONTROL
MXZ-2A MXZ-4A80VA
-
MXZ-5A
E2
Power
ON
OFF
Compressor
ON
OFF
Outside temperature
30min.
30min.
30min.
30min.
30min.
30min.
15min. 30min. 15min. 30min.
Pre-heat
ON
OFF
Breaker ON
20
:
Stop
operation
Start
operation
When outside
temperature is
above 20
:
The compressor is energized even while it is not operating.
This is to generate heat at the winding to improve the compressor's start-up condition.
12-9. COOL OPERATION
2. Coil frost prevention
The compressor operational frequency is controlled to prevent the indoor heat exchanger temperature from falling
excessively.
Compressor is turned OFF for 5 minutes when temperature of indoor coil thermistor continues 3: or less for 5 min-
utes or more.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
ON -1
:
or more
OFF less than -1
:
-1
:
-0.7
:
Room temperature minus
set temperature (During operation)
Room temperature minus
set temperature (Initial)
Thermostat