9
[2] Standard operation data <Split>
Reference data (connect to Plate HEX)
(1) PUHZ-HRP • V/YHA2
ACH50-50 plates
Mode
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Total
Capacity
W
7,100
8,000 10,000
11,200 12,500
14,000
Input
kW
2.20
1.82
3.67
2.61
4.80
3.50
Electrical circuit
Outdoor unit
PUHZ-HRP71VHA2
PUHZ-HRP100VHA2/
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
Phase, Hz
1, 50
1/3, 50
3, 50
Voltage
V
230
230 / 400
400
Current
A
9.9
8.2
16.5/5.6
11.7/4.0
7.3
5.3
Refrigerant circuit
Discharge pressure
MPa
2.4
2.0
2.6
2.1
2.8
2.3
Suction pressure
MPa
0.8
0.7
0.8
0.7
0.8
0.7
Discharge temperature
:
70
60
78
63
84
70
Condensing temperature
:
42
35
46
36
47
39
Suction temperature
:
12
6
11
4
10
3
Evaporating temperature
:
5
2
5
2
5
1
Evaporator inlet temperature
:
5
—
5
—
5
—
Evaporator outlet temperature
:
5
—
5
—
5
—
Condenser inlet temperature
:
—
55
—
60
—
65
Condenser outlet temperature
:
—
33
—
31
—
30
Water
conditions
Flow volume
L/min
20.4
22.9
28.7
34.4
35.8
40.1
Outlet water temperature
:
7
35
7
35
7
35
Outdoor
conditions
Intake air temperature
D.B.
:
35
7
35
7
35
7
W.B.
:
24
6
24
6
24
6
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/
F
)