2.4. Switch setting of FTC
Set the dip switch on the FTC (PCB) according to the following table.
System
ON/OFF
Input
Change mode
Input
Change TEMP.
Input
Outdoor unit *4
SW1-1 SW1-2 SW1-5 SW1-6 SW6-1 SW6-2
BASIC
External input
(non-voltage contact)
External input
(non-voltage contact)
DIP switch on PCB
SW2-1~8, SW3-1~3
SPLIT type
ON
OFF
OFF
ON
OFF
OFF
PACKAGED type
ON
OFF
ON
ON
OFF
OFF
External input
(non-voltage contact)
External input
(non-voltage contact)
Wired remote controller
SPLIT type
ON
OFF
OFF
OFF
OFF
OFF
PACKAGED type
ON
OFF
ON
OFF
OFF
OFF
ANALOG
TEMP.
External input or
4-20mA *1
External input
(non-voltage contact)
4-20mA
SPLIT type
OFF
ON
OFF
OFF
ON
ON
PACKAGED type
OFF
ON
ON
OFF
ON
ON
External input or
1-5V *2
External input
(non-voltage contact)
1-5V
SPLIT type
OFF
ON
OFF
OFF
OFF
ON
PACKAGED type
OFF
ON
ON
OFF
OFF
ON
External input
External input
(non-voltage contact)
0-10V
SPLIT type
ON
ON
OFF
OFF
OFF
OFF
PACKAGED type
ON
ON
ON
OFF
OFF
OFF
BASIC
and
SIMPLE
External input and
*3
Wired remote controller
External input and
*3
Wired remote controller
DIP switch on PCB
SW2-1~8, SW3-1~3
SPLIT type
OFF
OFF
OFF
ON
OFF
OFF
PACKAGED type
OFF
OFF
ON
ON
OFF
OFF
External input and
*3
Wired remote controller
External input and
*3
Wired remote controller
Wired remote controller
SPLIT type
OFF
OFF
OFF
OFF
OFF
OFF
PACKAGED type
OFF
OFF
ON
OFF
OFF
OFF
SIMPLE
Wired remote controller
Wired remote controller
Wired remote controller
SPLIT type
OFF
OFF
OFF
OFF
OFF
OFF
PACKAGED type
OFF
OFF
ON
OFF
OFF
OFF
*1: 4-20mA
····
OFF: 0~2mA
*2: 1-5V
····
OFF: 0~0.5V
*3: The command from the external input is prior to the one from the wired remote controller.
*4: SPLIT type : the standard outdoor unit without a plate HEX(refrigerant-water) inside.
PACKAGED type : the Air to Water outdoor unit with a plate of HEX(refrigerant-water) inside
OTHER SWITCH SETTING
SW1-3 Prohibition of Cooling mode
SW1-3=OFF : Operation mode Heating/HeatingECO/HotWater/Anti-freeze/Cooling
SW1-3=ON : Operation mode Heating/HeatingECO/HotWater/Anti-freeze
SW1-4 SW3-4,5,8 Not in use. Set to OFF. (Initial setting)
SW3-7 Not in use. Set to ON. (Initial setting)
SW3-6 Logic of Forced Comp. OFF external signal(TB142 5-6)
SW3-6
TB142 No.5-6 input
Item
OFF
OFF(open)
Normal
ON(short)
Forced Comp. OFF
ON
OFF(open)
Forced Comp. OFF
ON(short)
Normal
SW1-6,7,8 Set temperature range
SW1-6=OFF Set temperature range with wired remote controller
SW1-6=ON Set temperature table with DIP switch of FTC
SW1-6
SW1-7
SW1-8
Temperature range with wired remote controller
Temperature table
SW2-1~8, SW3-1~3
Heating/HeatingECO/Hot Water
Anti-Freeze
Cooling
OFF
OFF
OFF
Upper 55 ˚C / lower 20 ˚C
Upper 45 ˚C / lower 5 ˚C
Upper 25 ˚C / lower 5 ˚C
—
OFF
ON
OFF
Upper 60 ˚C / lower 20 ˚C *1
Upper 45 ˚C / lower 5 ˚C
Upper 25 ˚C / lower 5 ˚C
—
OFF
OFF
ON
Upper 50 ˚C / lower 20 ˚C
Upper 45 ˚C / lower 5 ˚C
Upper 25 ˚C / lower 5 ˚C
—
OFF
ON
ON
—
—
—
—
ON
OFF
OFF
—
—
—
Table
1
ON
ON
OFF
—
—
—
Table
2
ON
OFF
ON
—
—
—
—
ON
ON
ON
—
—
—
—
*1. Don’t use this setting when you use the standard outdoor unit without a plate HEX(Refrigerant-water) inside.