75
Set OFFSET temperature
T(h) in HEATING mode with [TEMP] buttons (
and
)
.
Ӡ
Set OFFSET temperature
T(c) in COOLING mode with [TEMP] buttons (
and
)
.
Ӡ
♦
In order to let the PCB memorize the changed parameters
Make sure to press the
button
before quitting the INITIAL SETTING mode.
If you press the
button
in INITIAL SETTING mode before pressing the
button
,
you can exit from this mode without any change.
FTC
Outdoor unit
TH1
Water
piping
T(a)=
Actual Flow water
temp.(outlet side)
T(s)=
sensed flow water
temp.
*1 Refrigerant-water HEX
FTC
Outdoor unit
TH1
Water
piping
T(a)=
Actual Flow water
temp.(outlet side)
T(s)=
sensed flow water
temp.
HEATING mode
Ӡ
T(h)
=T(a)-T(s)
COOLING mode
Ӡ
T(c)
=T(s)-T(a)
CIR.WATER
CIR.WATER
ON/OFF
TEMP OFFSET
HEATING
TEMP OFFSET
COOLING
*1
*1
<Temperature OFFSET setting>
This setting is to adjust the difference between the actual fl ow water temperature at the refrigerant-water heat exchanger outlet
and the temperature sensed by TH1 which tends to be lower due to heat leakage from water piping.