TM_i-BX(-N)_NC05_00_06_20_EN
MEHITS S.p.A.
●
TECHNICAL MANUAL
Version NC05 - Translation of the Original Instructions
16
Num Par
Description
Default
Unit
Min.
Max.
P010H
Type of integration for plant boiler(0: Integration; 1: Replace)
0
-
0
1
P010J
Plant set from external 0-5V(0:NO; 1:YES)
0
-
0
1
P010L
External low temperature setpoint limit (Winter)
15.0
°C
0
P010N
P010M
External setpoint signal start value in Winter
0.0
%
0
100.0
P010N
External high temperature setpoint limit (Winter)
25.0
°C
P010L
999.9
P010P
External setpoint signal end value in Winter
100.0
%
0
100.0
P010R
External low temperature setpoint limit (Summer)
18.0
°C
0
P010N
P010T
External setpoint signal start value in Summer
0.0
%
0
100.0
P010U
External High temperature setpoint limit (Summer)
30.0
°C
P010L
999.9
P0110
Setpoint for winter floor operation
14.0
°C
0
999.9
P0111
Setpoint for summer floor operation
25.0
°C
0
999.9
P0112
Setpoint for winter floor + fan coil operation
5.0
°C
0
999.9
P0113
Differential for winter floor + fan coil operation
2.0
°C
1.0
99.9
P0114
Type of device HT1 (0: Serial probe; 1: N-THC)
1
-
0
1
P0115
Type probe HT1 (0: Temperature; 1: TempHumidity)
1
-
0
1
P0116
Type of device HT2 (0: Serial probe; 1: N-THC)
1
-
0
1
P0117
Type probe HT2 (0: Temperature; 1: TempHumidity)
1
-
0
1
P0118
Type of device HT33 (0: Serial probe; 1: N-THC)
1
-
0
1
P0119
Type probe HT3 (0: Temperature; 1: TempHumidity)
1
-
0
1
P011A
External setpoint signal end value in Summer
100.0
%
0
100.0
P011B
Configuration NO11 (0: RECIRCULATION DHW; 1: DEHUMIDIFIER;2: PUMP HT1; 3:
SUMMER/WINTER)
0
-
0
3
P011C
Configuration DI10 (0: DEHUMIDIFIER; 1: FLUSSOSTAT RECIRC.DHW; 2: BACKUP BOILER)
1
-
0
2
P011D
Reletionship between plant and ambient (0: Unit work on ambient request; 1:Unit work
indipendent)
1
-
0
1
P011E
Differential to activate the high temperature zone
1.0
°C
0.1
9.9
P011F
Differential to activate the low temperature zone
1.0
°C
0.1
9.9
P011L
Type of device room 6 (0: Serial probe; 1: N-THC)
1
-
0
1
P011M
Type device 6 (0: Temperature; 1: TempHumidity)
1
-
0
1
P011N
Type of regulation of mixed circuit pump LT3 (0: Always on; 1: On ambient request)
1
-
0
1
P011P
Combination with zone HT
0
-
0
3
P011R
Fix set winter LT3
38.0
°C
P015R
P015T
P011T
Enable outdoor reset summer LT3
0
-
0
1
P011U
Fixed setpoint for 3rd mixed circuit (Summer)
19.0
°C
P015M P015P
P0120
Type of device room 4 (0: Serial probe; 1: 1: N-THC)
1
-
0
1
P0121
Type device 4 (0: Temperature; 1: TempHumidity)
1
-
0
1
P0122
Type of regulation of mixed circuit pump LT1 (0: Always on; 1: On ambient request)
1
-
0
1
P0123
Combination with zone4 HT
0
-
0
3
P0124
Type of device room 5 (0: Serial probe; 1: N-THC)
1
-
0
1
P0125
Type device 5 (0: Temperature; 1: TempHumidity)
1
-
0
1
P0126
Type of regulation of mixed circuit pump LT2 (0: Always on; 1: On ambient request)
1
-
0
1
P0127
Combination with zone5 HT
0
-
0
3
P0140
Antifreeze Room SetPoint
5.0
°C
-10
999
P0141
Setpoint external temperature for sniffer antifreeze
4.0
°C
-9999
9999
P0142
Differential external temperature for sniffer antifreeze
1.0
°C
0
999
P0143
Type of configuration of plant pump (0: On; 1: Sniffer)
1
-
0
1
P0144
Time on sniffer DHW (in tenth of second)
12
s
0
500
P0145
Delay time between 2 sniffers DHW (in tenth of second)
18
s
0
500
P0146
Nurber of curve for plant
4
-
1
4
P0147
Time on sniffer plant (in tenth of second)
18
s
0
9999
P0148
Delay time between 2 sniffers plant (in tenth of second)
5
min
0
9999
P0149
Enable the antifreeze for plant circuit (0:NO; 1:YES)
1
-
0
1
P0150
Time on sniffer antifreeze (in tenth of second)
6
s
0
500