TM_i-BX(-N)_NC05_00_06_20_EN
MEHITS S.p.A.
●
TECHNICAL MANUAL
Version NC05 - Translation of the Original Instructions
61
case b)
(ref. paragraph “
”) no “MaxSet” message and if installed the DHW heater will turn on following the overboost setpoint. Otherwise
-
only for 3-way DHW units - the delivery heater will come on, following the DHW setpoint (ECONOMY or COMFORT setpoint)
Meaning that with
0202
= 1 and
0300
= 1 (only Heat pump + Delivery heater), in case of heat pump inhibition the delivery heater will be used to satisfy
the DHW setpoint.
DHW heater
Delivery heater
Whenever the unit stops producing DHW, it becomes available for the production of system water.
For the default values of the various parameters, see the parameters table
ON
OFF
DHW storage tank T
(B3)
Compressor
Overboost diff.
(0210)
Proportional band DHW
(0513)
DHW setpoint
(0022 or 0023)
Storage tank in heating
Heater
DHW
ON
OFF
Overboost Set
(0209)
Compressor block
Storage tank in cooling
ON
OFF
DHW storage tank T
(B3)
Compressor
Proportional band DHW
(0513)
DHW setpoint
(0022 or 0023)
Heater
At delivery
ON
OFF
Compressor block