FUNCTION DESCRIPTION
4.1
MACHINE MANAGEMENT
–
OPERATING MODES -
Parameter
130Z
(reversible units) indicates if the unit is an i-BX (chiller only) or i-BX-N (heat pump) unit.
The i-BX unit is defined through the following parameters:
130Z
= NO (non-reversible unit)
130X
= CHILLER
The i-BX-N unit is defined through the following parameters:
130Z
= YES (reversible unit)
130X
parameter non visible
In case of i-BX-N units, use parameter
0202
to enable DHW (default value = 0).
Parameter
0202
is only available for i-BX-N units.
With i-BX-N units with DHW enabled it is possible to set the system / DHW priority using parameter
0014
(default value = DHW).
It will be possible to set the machine operating modes using the menu or the digital input (the operating mode type selection is possible using
parameter
0100
: “
BY KEYBOARD
” or
“BY
DIGITAL INPUT
”).
4.1.1
MODE SELECTION USING THE MENU
0100= BY KEYBORAD
Mode change
using the machine keypad (pldPro)
Press
to access the operation
settings window
COOL+DHW (priority DHW)
COOL
HEAT+DHW (priority DHW)
HEAT (only plant)
DHW (only)
4.1.2
MODE SELECTION FROM DIGITAL INPUT
0100= BY DIGITAL INPUT
N
Contacts
Summer/Winter
Mode
Mode
DI5/SA2
DI6/SA3
DI7/SA3
Clamps
25-27
25-28
25-29
1
COOL+DHW (priority DHW)
CLOSE
OPEN
OPEN
2
COOL (only plant)
CLOSE
OPEN
CLOSE
3
HEAT+DHW (priority DHW)
OPEN
OPEN
OPEN
4
HEAT (only plant)
OPEN
OPEN
CLOSE
5
DHW (only)
---
CLOSE
OPEN