5.2.3
HP + DHW STORAGE HEATER (P0202=3) OR DELIVERY HEATER (P0202=1 AND P0300=1)
The heat pump will work as described in paragraph “
,
with the following differences:
case a)
(ref. paragraph “
”) once the DHW setpoint has been reached (
0022
,
0023
) the DHW heater comes on with a fixed delay of 30s,
following the overboost setpoint (
0209
). When this setpoint has been reached, it will turn on again at
0209
-
0210
and turn off at
0209
, or, if the storage
tank water temperature continues to decrease, when
0022
or
0223
is reached, depending on the function below
ON
OFF
DHW storage tank T
(B3)
Compressor
Overboost diff.
(0210)
Proportional band DHW
(0513)
DHW setpoint
(0022 or 0023)
Storage tank in heating
Storage tank in cooling
Heater
DHW
ON
OFF
Overboost Set
(0209)