TM_i-BX(-N)_NC05_00_06_20_EN
MEHITS S.p.A.
●
TECHNICAL MANUAL
Version NC05 - Translation of the Original Instructions
21
Num Par
Description
Default
Unit
Min.
Max.
P0814
Set temperature end defrost
0.0
°C
-999.9
999.9
P0815
Enable dynamic defrost function (0:NO; 1:YES)
1
-
0
1
P0816
Dynamic defrost - External temperature threshold
0.0
°C
-999.9
999.9
P0817
Dynamic defrost setpoint differential
1.5
Bar
-999.9
999.9
P0818
Dynamic defrost proportional band
15.0
°C
-999.9
999.9
P0819
Out of envelope alarm delay during defrost
900
s
0
32000
P0820
Max. increase speed rate (going to target speed in defrost) [rps/s]
2.0
rps/s
0
9.9
P0821
Maximum number of hours with no defrost
0
h
0
999
P0822
Enable force defrost by elapsed time from last defrost (0:NO; 1:YES)
0
-
0
1
2.4.10
MENÙ 09
Num Par
Description
Default
Unit
Min.
Max.
P0982
Reverse logic digital input 4 (0: NORMALLY CLOSED; 1: NORMALLY OPEN)
1
-
0
1
P0983
Reverse logic digital input 5 (0: NORMALLY CLOSED; 1: NORMALLY OPEN)
0
-
0
1
P0984
Reverse logic digital input 6 (0: NORMALLY CLOSED; 1: NORMALLY OPEN)
0
-
0
1
P0985
Reverse logic digital input 7 (0: NORMALLY CLOSED; 1: NORMALLY OPEN)
0
-
0
1
P0986
Reverse logic digital input 8 (0: NORMALLY CLOSED; 1: NORMALLY OPEN)
1
-
0
1
P0987
Reverse logic digital input 9 (0: NORMALLY CLOSED; 1: NORMALLY OPEN)
1
-
0
1
P0988
Enable external serial probe for outdoor reset (0:NO; 1:YES)
0
-
0
1
2.4.11
MENÙ 10
Num Par
Description
Default
Unit
Min.
Max.
P1000
Calibration value B1 probe
0.0
-99.9
99.9
P1001
Calibration value B2 probe
0.0
-99.9
99.9
P1002
Calibration value B3 probe
0.0
-99.9
99.9
P1003
Calibration value B4 probe
0.0
-99.9
99.9
P1004
Calibration value B5 probe
0.0
-99.9
99.9
P1005
Calibration value B6 probe
0.0
-99.9
99.9
P1006
Calibration value B7 probe
0.0
-999.9
999.9
P1007
Calibration value B8 probe
0.0
-99.9
99.9
P1008
Calibration value B9 probe
0.0
-99.9
99.9
P1009
Calibration value B10 probe
0.0
-99.9
99.9
P100H
Enable switching on digital output NO7 with minor alarms (0:NO; 1:YES)
0
-
0
1
P1010
Calibration value B11 probe
0.0
°C
-99.9
99.9
P1011
Calibration value B12 probe
0.0
°C
-99.9
99.9
P101A
Filter B1
5
-
0
7
P101B
Filter B2
1
-
0
7
P101C
Filter B3
5
-
0
7
P101D
Filter B4
5
-
0
7
P101E
Filter B5
5
-
0
7
P101F
Filter B6
5
-
0
7
P101G
Filter B7
5
-
0
7
P101H
Filter B8
5
-
0
7
P101I
Filter B9
5
-
0
7
P101J
Filter B10
5
-
0
7
P101K
Filter B11
5
-
0
7
P101L
Filter B12
5
-
0
7
P101M
Ain filter enable (0:NO; 1:YES)
1
-
0
1