TM_i-BX(-N)_NC05_00_06_20_EN
MEHITS S.p.A.
●
TECHNICAL MANUAL
Version NC05 - Translation of the Original Instructions
15
2.4
PARAMETERS TABLE
The following table lists the controller parameters and the relative maximum and minimum values.
CAUTION:
The Default column of the following table only shows the values assigned to the parameters relating to the i-BX-N 013M
unit.
Changing the value of some parameters causes the value of others to change automatically, so it is recommended to check
the parameters again at the end of the parameter setting.
2.4.1
MENU 00
Part n.
Description
Default
Unit
Min.
Max.
P0010
Unit of measure (0:***; 1: STANDARD(ßC - barg); 2: ANGLO-SAXON(ßF - psig))
1
-
0
2
P0014
Priority of the system (0: Plant; 1: DHW)
1
-
0
1
P0017
Set zone operation mode (0: OFF; 1: ON)
0
-
0
1
P0018
Set zone operation mode (0: OFF; 1: ON)
0
-
0
1
P0019
Set zone operation mode (0: OFF; 1: ON)
1
-
0
1
P0020
Set zone operation mode (0: OFF; 1: ON)
0
-
0
1
P0021
Set zone operation mode (0: OFF; 1: ON)
0
-
0
1
P0022
Setpoint energy saving for DHW
44.0
°C
P1410
P015U
P0023
Setpoint comfort for DHW
48.0
°C
P1410
P015U
P0024
Room setpoint comfort in summer mode HT1
25.0
°C
5.0
32.0
P0025
Room setpoint comfort in winter mode HT1
20.0
°C
5.0
32.0
P0026
Room setpoint comfort in summer mode HT2
25.0
°C
5.0
32.0
P0027
Room setpoint comfort in winter mode HT2
20.0
°C
5.0
32.0
P0028
Room setpoint comfort in summer mode HT3
25.0
°C
5.0
32.0
P0029
Room setpoint comfort in winter mode HT3
20.0
°C
5.0
32.0
P0030
Room setpoint comfort in summer mode LT1
25.0
°C
5.0
32.0
P0031
Room setpoint comfort in winter mode LT1
18.0
°C
5.0
32.0
P0032
Room setpoint comfort in summer mode LT2
25.0
°C
5.0
32.0
P0033
Room setpoint comfort in winter mode LT2
18.0
°C
5.0
32.0
P0034
Date format (1: dd/mm/yy; 2: mm/dd/yy; 3: yy.mm.dd)
1
-
1
3
P0054
Set zone operation mode (0: OFF; 1: ON)
0
-
0
2
P0060
Room setpoint comfort in summer mode
23.0
°C
5.0
32.0
P0061
Room setpoint comfort in winter mode
23.0
°C
5.0
32.0
P0062
Change the working mode of unit by keyboard (0: OFF; 1: ON)
0
-
0
1
P0063
N-THC small area selection (0: Clock; 1: Room temperature; 2: Temperature setp; 3: Room
humidity; 4: Humidity setp; 5: External temperature)
0
-
0
5
P0100
Change mode by keyboard or DIN (0: BY DIGITAL INPUTS; 1: BY KEYBOARD)
0
-
0
1
2.4.2
MENÙ 01
Num Par
Description
Default
Unit
Min.
Max.
P0100
Change mode by keyboard or DIN (0: BY DIGITAL INPUTS; 1: BY KEYBOARD)
1
-
0
1
P0101
Configuration of zones
0
-
0
3
P0102
Number of sampling for average external temperature
50
-
0
100
P0103
Time of sampling for average external temperature
20
min
0
999
P0105
Enable auto summer/winter (0:NO; 1=YES)
0
-
0
1
P0106
Setpoint for changeover winter mode
16.0
°C
0
999.9
P0107
Differential for changeover winter mode
2.0
°C
1.0
999.9
P0108
Setpoint for changeover summer mode
24.0
°C
0
999.9
P0109
Differential for changeover summer mode
2.0
°C
1.0
99.9
P010G
Type of integration for plant (0: Integration; 1: Replace)
0
-
0
1