User area read/write method
1.12 User area read/write method
Inverter parameters
Pr.506 to
Pr.515, Pr.826 to
Pr.865
can be used as user parameters.
Since this parameter area and the devices used with the PLC function, D110 to D159,
are accessible to each other, the values set in
Pr.506 to Pr.515, Pr.826 to
Pr.865
can be
used in a sequence program. The result of operation performed in the sequence
program can also be monitored using
Pr.506 to Pr.515, Pr.826 to
Pr.865
.
1.12.1 User parameter read/write method
User parameter
(Pr.506 to Pr.515, Pr.826 to
Pr.865)
and device (D110 to D159) data can
be read/written freely. Data transfer between
Pr.506 to Pr.515, Pr.826 to
Pr.865
and D110
to D159 is executed automatically.
1) User parameter write processing and device write processing
When values are written to
Pr.506 to Pr.515, Pr.826 to
Pr.865
using the FR-PU04/FR-
PU07(-01) or computer link communication, they are written to the parameter
storing RAM area and EEPROM area, and further to D110 to D159 simultaneously.
2) User parameter read processing and device write processing.
When values are written to D110 to D159 from the PLC function side, they are
written to the parameter storing RAM area
(Pr.506 to Pr.515, Pr.826 to
Pr.865)
and
read using the FR-PU04/FR-PU07(-01) or communication(RS-485 or
communication option). (Since data are not written to the EEPROM, making power-
on reset returns the data to the original values.)
3) Processing performed at inverter reset or power restoration
When the inverter is reset, the
Pr.506 to Pr.515, Pr.826 to
Pr.865
values stored in the
EEPROM are transferred to the RAM area and D110 to D159.
Device
No.
Inverter
Parameter
No.
Name
Initial
Value
Setting
Range
Minimum Setting
Unit
Data Access
D110 to
D159
506 to 515,
826 to 865
User
parameters
0
0 to
65535
1
Always
enabled
POINT
Example of using the user parameter area
When the timing is to be changed for machine adjustment using D110 that
stores the timer setting, setting
Pr. 506
without modifying the program enters
the set data into D110, enabling adjustment.
Pr.506 to Pr.515,
Pr.826 to Pr.865
D110 to D159
Inverter parameters
PLC function devices
D110 to D159
3)
3)
1)
1)
2)
2)
1)
1)
FR-PU04/FR-PU07(-01)
or RS-485 communication
Pr.506 to Pr.515,
Pr.826 to Pr.865
(RAM)
Pr.506 to Pr.515,
Pr.826 to Pr.865
(EEPROM)
Содержание FR - F700
Страница 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Страница 7: ...VI MEMO ...
Страница 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Страница 207: ...200 MEMO ...
Страница 208: ...201 Chapter 1 Chapter 2 Chapter 3 Chapter 4 4 ERROR CODE LIST 4 1 How to read the error code 202 ...
Страница 211: ...204 MEMO ...
Страница 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...
Страница 216: ...FR F 700 INVERTER ...