99
Watchdog timer (operation clog up monitor timer)
3
SEQUENCE PROGRA
M
M
ING
3.15 Watchdog timer (operation clog up monitor timer)
(1) Watchdog timer
A watchdog timer is the internal timer of the built-in PLC function designed to
detect hardware or sequence program faults.
Its default value is set to 200ms.
(2) Watchdog timer resetting
The built-in PLC function resets the watchdog timer before execution of step 0
(after execution of END processing).
When the built-in PLC function operates properly and the END instruction is
executed within the setting in the sequence program, the watchdog timer does
not time out.
If the hardware fault of the built-in PLC function occurs or the scan time of the
sequence program is too long to execute the END instruction within the setting,
the watchdog timer times out.
Fig 3.23 Watchdog Timer Resetting
(3) Processing performed when watchdog timer times out
If the scan time exceeds the watchdog timer setting, a watchdog timer error
occurs and:
1) The built-in PLC function turns off all outputs.
2) The P.RUN LED goes off or flickers.
3) M9008 turns on and the error code is stored into D9008.
REMARKS
The watchdog timer setting can be changed by built-in PLC function parameter setting of GX
Developer. (Refer to the GX Developer manual for details.)
Sequence program
END
0
0
WDT resetting
(Internal processing)
Internal
processing time
Excess of scan time over setting
results in watchdog timer error.
Содержание FR - F700
Страница 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Страница 7: ...VI MEMO ...
Страница 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Страница 207: ...200 MEMO ...
Страница 208: ...201 Chapter 1 Chapter 2 Chapter 3 Chapter 4 4 ERROR CODE LIST 4 1 How to read the error code 202 ...
Страница 211: ...204 MEMO ...
Страница 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...
Страница 216: ...FR F 700 INVERTER ...