17
Device map
1
PL
C F
UNCT
ION
D
evi
ce
M
ap
1.9.5
Special registers
The special registers are data registers with special applications and therefore data
should not be written to the special registers in the program.
Number
Name
Description
Page
S
p
eci
a
l r
egi
st
e
rs
D9008
Self-diagnostic
error
Stores the self-diagnosed error number in BIN. (
Refer
to page 26
for the error codes.)
26
D9010
Operation error
step
Stores the step number in BIN, at which an instruction
execution error occurred. After that, data is updated
each time operation error occurs.
—
D9011
Operation error
step
Stores the step number in BIN, at which an instruction
error occurred. Since data is stored into D9011 when
M9011 turns from off to on, D9011 data is not updated
unless M9011 is cleared by the user program.
—
D9014
I/O control
method
3 (fixed): Both input and output refreshes
—
D9015
CPU operating
status
Stores the operating status of the PLC function.
—
D9016
Program number
Stores the number that indicates which sequence
program is currently in execution.
1 (fixed): Main program (RAM)
—
D9017
Minimum scan
time
(10ms units)
Stores the scan time at every END that is smaller than
D9017 data, i.e. stores the minimum scan time in BIN.
—
D9018
Scan time
(10ms units)
Stores and updates the scan time at every END in
BIN.
—
D9019
Maximum scan
time
(10ms units)
Stores the scan time at every END that is greater than
D9019 data, i.e. stores the maximum scan time in BIN.
—
D9062 to
D9093
Remote registers
Special registers for communication with the master
station in CC-Link.
56
D9133
Output frequency
monitor
Stores the current output frequency.
0.01Hz units
23
D9134
Output current
monitor
Stores the current output current.
0.01A/0.1A units
*
D9135
Output voltage
monitor
Stores the current output voltage.
0.1V units
* The setting depends on the inverter capacities.
(FR-F720-02330-NA (FR-F740-01160-NA/EC) or lower/FR-F720-03160-NA (FR-F740-01800-NA/EC) or
higher)
RUN
STOP
0
1
B15
B12B11
B8B7
B4B3
B0
RUN
STOP
0
1
RUN
STOP
0
1
Remote run/stop
using GX Developer
Remote run/stop using
sequence parameter setting
SQ signal
ON/OFF
Invalid
Содержание FR - F700
Страница 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Страница 7: ...VI MEMO ...
Страница 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Страница 207: ...200 MEMO ...
Страница 208: ...201 Chapter 1 Chapter 2 Chapter 3 Chapter 4 4 ERROR CODE LIST 4 1 How to read the error code 202 ...
Страница 211: ...204 MEMO ...
Страница 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...
Страница 216: ...FR F 700 INVERTER ...