39
Inverter status monitoring, special registers
for control
1
PL
C F
UNCT
ION
1.10.8 Monitor setting selection(D9215 to D9218)
Set the names and units of monitored items for each of D9216, D9217, and D9218
using the PR command.
(Refer to page 193.)
To display the names and the units of the monitored items, which are set by D9216 to
D9218, on FR-PU07-01, set "40, 41, or 42" in
Pr.774
to
Pr.776
. (Refer to the
Instruction
Manual of the inverter
for the details of
Pr.774
to
Pr.776
.)
Set D9215 as shown below to display the monitored values, which are set by D9216 to
D9218, with decimal points.
<Setting of D9215>
* The bits other than the ones above are ignored.
<Displayed decimal point setting>
Setting example:
1. To display the D9216 monitor without a decimal point in the first monitor
•
Set H0000 in D9215.
•
Set "40" in
Pr.774
.
2. To display the D9216 monitor in 0.1 increments in the first monitor and the D9218
monitor in 0.001 increments in the second monitor
•
Set H3100 in D9215.
•
Set "40" in
Pr.774
and "42" in
Pr.775
.
Device
Monitored item
Pr.774 to Pr.776 setting
D9216
User monitor 1
40
D9217
User monitor 2
41
D9218
User monitor 3
42
bn+1
bn
Unit
0
0
1 increment
(without decimal point)
0
1
0.1 increment
1
0
0.01 increment
1
1
0.001 increment
B15
B12B11
B8B7
B4B3
B0
Select the displayed decimal point for the D9216 monitor.
Select the displayed decimal point for the D9217 monitor.
Select the displayed decimal point for the D9218 monitor.
Содержание FR - F700
Страница 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Страница 7: ...VI MEMO ...
Страница 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Страница 207: ...200 MEMO ...
Страница 208: ...201 Chapter 1 Chapter 2 Chapter 3 Chapter 4 4 ERROR CODE LIST 4 1 How to read the error code 202 ...
Страница 211: ...204 MEMO ...
Страница 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...