40
Inverter parameter read/write method
1.11 Inverter parameter read/write method
1.11.1 Reading the inverter parameters
When reading the parameter, the parameter description is stored to D9242(D9244) by
storing the parameter number to D9241(D9243) and turning Y28 (Y2A) on. When
reading is completed, X28 (X2A) turns ON to notify the completion. (The device
number within parentheses is used to read the parameter setting value from
EEPROM.)
When reading the calibration parameter (
Pr. 902
to
Pr. 939
), set the following value to
D9234 (D9235) to read each calibration parameter value.
0: Setting value (Frequency)
1: Parameter-set analog value
2: Analog value input from terminal
When access error occurs such as "parameter does not exist", value obtained by adding the
parameter number and 8000H is stored to D9150.
(Refer to page 37)
Device No.
Name
Command Completion
Data Access Enable
Condition
(Operation mode)
D9241
Parameter number (RAM)
Y28
X28
Always
D9242
Parameter description (RAM)
D9234
Second parameter changing
(RAM)
D9243
Parameter number (EEPROM)
Y2A
X2A
D9244
Parameter description
(EEPROM)
D9235
Second parameter changing
(EEPROM)
Содержание FR - F700
Страница 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Страница 7: ...VI MEMO ...
Страница 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Страница 207: ...200 MEMO ...
Страница 208: ...201 Chapter 1 Chapter 2 Chapter 3 Chapter 4 4 ERROR CODE LIST 4 1 How to read the error code 202 ...
Страница 211: ...204 MEMO ...
Страница 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...
Страница 216: ...FR F 700 INVERTER ...