25
Inverter status monitoring, special registers
for control
1
PL
C F
UNCT
ION
(3) Fault clear signal (X51 signal)
The X51 signal cancels a fault without resetting the inverter when an inverter fault
occurs.
The X51 signal cancels an inverter fault while the PLC function operation continues.
Enable the X51 signal by setting "51" in any of
Pr.178 to Pr.189 (Input terminal function
selection)
in advance.
• Fault clear from the X51 signal is invalid during the retry operation (including the
waiting time for a retry).
(The X51 signal is available when the retry count excess (E.RET) occurs.
• If a fault clear is performed, start commands from PU and communication are also
cleared. (The statuses other than start command from communication remain the
same at a fault clear.)
REMARKS
•
E.CPU, E.P24, E.1, E.2, E.6, E.7, E.13, E.PE2 cannot be cleared by the X51 signal.
CAUTION
•
The cumulative heat values of the electronic thermal relay and the
regenerative brake are not cleared at a fault clear. A fault like E.THM, E.THT,
E.BE may occur again.
•
The inverter is in stop status immediately after a fault clear. However, the
inverter restarts its operation after the fault is cleared when a start command
has been ON.
•
Pressing the STOP/RESET key on the operation panel or parameter unit
activates a normal reset at a fault occurrence. Take caution not to press it by
accident.
•
Changing the terminal assignment using
Pr.178 to Pr.189 (Input terminal function
selection)
may affect the other functions. Set parameters after confirming the
function of each terminal.
X51 signal
OFF
ON
ON
OFF
OFF
ON
Fault occurs
If a fault occurs while the X51
signal has been ON, turn OFF
the X51 signal once, then turn it
ON again.
Fault is cleared by
turn ON of X51 signal.
If a fault occurs while the X51 signal has
been ON, the fault is not cleared.
Fault status
(terminal ABC)
Fault is cleared by turn
ON of X51 signal.
Содержание FR - F700
Страница 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Страница 7: ...VI MEMO ...
Страница 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Страница 207: ...200 MEMO ...
Страница 208: ...201 Chapter 1 Chapter 2 Chapter 3 Chapter 4 4 ERROR CODE LIST 4 1 How to read the error code 202 ...
Страница 211: ...204 MEMO ...
Страница 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...
Страница 216: ...FR F 700 INVERTER ...