3.18 Setting of output (Y) status at switching from
STOP status to RUN status
When the RUN status is switched to the STOP status, the outputs (Y) in the RUN
status are stored into the built-in PLC function.
Using the built-in PLC function parameter, you can set whether the outputs (Y) will be
output again or will be output after execution of operation when the STOP status is
switched to the RUN status.
"Output (Y) status at STOP is output"
The sequence program operation is performed after the output (Y)
status at the time of entering the STOP status is output.
"Outputs (Y) are cleared (output one scan later)"
The outputs (Y) are all cleared, and after execution of the sequence
program operation, the outputs are provided.
Fig 3.24 Processing Performed when STOP Status Is Switched to RUN Status
Output (Y) status at the time of
entering the STOP status is output.
Sequence program operation is executed.
STOP status to RUN status
Is output (Y) status at
STOP to be output?
Output (Y) status is cleared.
YES
NO
Содержание FR - F700
Страница 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Страница 7: ...VI MEMO ...
Страница 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Страница 207: ...200 MEMO ...
Страница 208: ...201 Chapter 1 Chapter 2 Chapter 3 Chapter 4 4 ERROR CODE LIST 4 1 How to read the error code 202 ...
Страница 211: ...204 MEMO ...
Страница 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...
Страница 216: ...FR F 700 INVERTER ...