36
Inverter status monitoring, special registers
for control
(2) Inverter operation status control enable/disable setting (D9149)
You can enable or disable D9148 "inverter operation status control". The controls
of the corresponding bits of D9148 are enabled by turning on/off (1, 0) bits b0 to
b11 of D9149. All bits are factory-set to "0".
Example: When H1F is set to D9149, bits b0 to b11 are 1 (ON), the external terminal
inputs are therefore all disabled, and operation control using the inverter
operation status control (D9148) can be performed.
<Operation command setting program example>
The following program example runs the inverter at high speed in forward rotation
direction.
CAUTION
•
When D9148 "inverter operation status control" is enabled using D9149,
the control performed by external terminal inputs and the control
performed by CC-Link remote inputs are disabled for the enabled bits.
(Same as when "No functions" are set to
Pr.178
to
Pr.189
.)
•
When the terminal is made valid from PLC function, control from external
terminal is made invalid.
•
The SQ signal can be input from external terminals at any time.
(The SQ signal cannot be controlled with bits from D9149.)
B15
B12B11
B8B7
B4B3
B0
0:OFF
1:ON
STF (Pr.178)
STR (Pr.179)
RH (Pr.182)
RM (Pr.181)
RL (Pr.180)
JOG (Pr.185)
RT (Pr.183)
AU (Pr.184)
CS (Pr.186)
MRS (Pr.187)
STOP (Pr.188)
RES (Pr.189)
Invalid
1
1
1
1
1
1
1
1
1
1
1
1
Operation start
Operation stop
Turns on operation start pulse.
Enables all inverter operation status
control enable/disable bits, and
disables external terminal inputs.
Self-holds operation start, and turns
on bits 0 (STF) and 2 (RH) of inverter
operation status control, D9148.
At input of stop signal, clears inverter
operation status control, D9148,
to 0 and decelerates inverter to stop.
HFFF
Содержание FR - F700
Страница 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Страница 7: ...VI MEMO ...
Страница 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Страница 207: ...200 MEMO ...
Страница 208: ...201 Chapter 1 Chapter 2 Chapter 3 Chapter 4 4 ERROR CODE LIST 4 1 How to read the error code 202 ...
Страница 211: ...204 MEMO ...
Страница 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...
Страница 216: ...FR F 700 INVERTER ...