8. Connections of I/O Interface
8.2 Connecting with Remote I/O Unit
104
8.2.8 Connection of FCUA-DX10 /14 Unit and Machine Control Signal
Input Output
Type of machine input/output
signal and No. of points
32 points
32 points
DO-L
R300 cable/
R301 cable
Machine
signal
DI-L
R300 cable/
R301 cable
Machine
signal
FCUA-DX10
or
FCUA-DX14
The remote I/O unit cable types include the R300 and R301 types. The R300 cable has one end cut off, and
the R301 cable is used for connection to the IDEC terminal block BX1F-T40A
(Note 1)
. The R300-3M and
R301-3M cables are available. If a cable longer than 3m is required, use the CN300 and CS301 connector set.
The one-end CN300 connector (optional, with one end) includes the DI-L (DI-R) and DO-L (DO-R) connectors.
The CS301 connector set (optional with both ends) includes the DI-L and DO-L connectors, and two
connectors for connection with the terminal block (IDEC).
(Note 1)
IDEC I/O terminal BX1F-T40
24VDC(+)
24VDC(+)
Machine
control panel
DI-L
FCUA-DX100/140
COM
A
3
B1
B2
A1
A2
B1
B2
A1
A2
2.2k
Ω
Input circuit
Sink type
Output circuit
Sink type
DO-L
0V
(RG)
RA
PL
Control
circuit
Stabilized power supply
DCIN
24VDC(+) 0V FG
1 2 3
RIO2
RIO1
F
24VDC(+)
DI-L
FCUA-DX101/141
COM
A3
B3
B1
B2
A1
A2
B1
B2
A1
A2
2.2k
Ω
Input circuit
Source type
Output circuit
Source type
DO-L
0V(RG)
RA
PL
DCIN
24VDC(+) 0V FG
1 2 3
RIO2
RIO1
F
0V(RG)
Machine
control panel
Stabilized power supply
Control
circuit
<Outline of connection>
CAUTION
Incorrect connections could damage the device, so always connect the cable to the designated
connector.
Do not connect or disconnect the connection cables between each unit while the power is ON.