II
Restrictions ]
- 40 -
HWE0716A
GB
[8] Restrictions on Pipe Length
(1) End branching
HP72, HP96 models
Unit: m [ft]
Operation
Pipe sections
Allowable length of
pipes
Length
Total pipe length
A+B+C+D
+a+b+c+d+e+f
300 [984] or less
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
A+B+C+c or
A+D+f
150 [492] or less
(Equivalent length 175
[574] or less)
Total pipe length from the first branch to the far-
thest indoor unit (
)
B+C+c or
D+f
40 [131] or less
Height
difference
Between indoor and
outdoor units
Outdoor unit above in-
door unit
H
50 [164] or less
Outdoor unit below in-
door unit
H'
40 [131] or less
Between indoor units
h
15 [49] or less
L
B
e
h
f
6
1
a
c
b
3
2
5
A
D
C
d
4
H
H
'
Branch joint
Indoor Indoor
Indoor
Indoor Indoor Indoor
cap
Branch header
(Outdoor unit above indoor unit)
(Outdoor unit below indoor unit)
Outdoor unit
First branch
(Branch joint)
Содержание City Multi PUHY-HP144TSHMU-A
Страница 1: ......
Страница 9: ...HWE0716A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 53: ... 44 ...
Страница 63: ... 54 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 76: ... 67 HWE0716A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 69 2 Principal Parts and Functions 70 ...
Страница 77: ... 68 ...
Страница 83: ... 74 ...
Страница 85: ... 76 ...
Страница 109: ... 100 ...
Страница 125: ... 116 ...
Страница 220: ... 211 HWE0716A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 213 ...
Страница 221: ... 212 ...
Страница 265: ......