IX
Troubleshooting ]
- 200 -
HWE0716A
GB
(3) Trouble treatment when the main power breaker is tripped.
Items to be checked
Phenomena
Remedy
[1]
Perform Meg check between the
terminals on the power terminal
block TB1.
Zero to several ohm, or Meg failure Check each part in the main inverter
circuit.
*Refer to "Simple checking Proce-
dures for individual components of
main inverter circuit".
Diode stack
IPM
Rush current protection resistor
Electromagnetic relay
DC reactor
[2]
Turn on the power again and
check again.
1)
Main power breaker trip
2)
No remote control display
[3]
Turn on the outdoor unit and check
that it operates normally.
1)
Operates normally without tripping
the main breaker.
a) The wiring may have been short-
circuited. Search for the wire that
short-circuited, and repair it.
b) If item a) above is not the cause of
the problem, the compressor may
have a problem.
2)
Main power breaker trip
A compressor ground fault can be con-
sidered. Go to (2)-[2].
Содержание City Multi PUHY-HP144TSHMU-A
Страница 1: ......
Страница 9: ...HWE0716A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 53: ... 44 ...
Страница 63: ... 54 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 76: ... 67 HWE0716A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 69 2 Principal Parts and Functions 70 ...
Страница 77: ... 68 ...
Страница 83: ... 74 ...
Страница 85: ... 76 ...
Страница 109: ... 100 ...
Страница 125: ... 116 ...
Страница 220: ... 211 HWE0716A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 213 ...
Страница 221: ... 212 ...
Страница 265: ......