IX
Troubleshooting ]
- 171 -
HWE0716A
GB
1. Error
Code
Function setting error
2. Error definition and error detection method
Resistor connection error
3. Error source, cause, check method and remedy
1. Error
Code
Model setting error
2. Error source, cause, check method and remedy
1. Error
Code
Incompatible unit combination
2. Error definition and error detection method
The check code will appear when the indoor units with different refrigerant systems are connected.
3. Error source, cause, check method and remedy
7113
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Wiring failure
1)
Control board connector
Check the CNTYP4,5 connector connection.
Inverter board connector
Check the CNTYP connector connection
(2)
Disconnected connector, short cir-
cuit, contact failure
2)
Check the compatibility of the circuit board, and replace
it with a correct one if necessary.
(3)
Incompatibility between the control
board and inverter board (Replace-
ment of the circuit board with the
wrong one)
3)
Check the model selection switch on the outdoor unit
(Dipswitch SW5-7 on the control board.).
7117
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Wiring failure
1)
Control board connector
Check the CNTYP4,5 connector connection.
Inverter board connection
Check the CNTYP connector connection
(2)
Disconnected connector, short circuit, contact
failure
7130
Error source
Cause
Check method and remedy
Outdoor unit
The connected indoor unit is for use with R22
or R407C. Incorrect type of indoor units are
connected.
The M-NET connection adapter is connected
to the indoor unit system in a system in which
the Slim Model (A control) of units are con-
nected to the M-NET.
Check the connected indoor unit model.
Check whether the connecting adapter for
M-NET is not connected to the indoor unit.
(Connect the connecting adapter for M-NET
to the outdoor unit.)
Содержание City Multi PUHY-HP144TSHMU-A
Страница 1: ......
Страница 9: ...HWE0716A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 53: ... 44 ...
Страница 63: ... 54 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 76: ... 67 HWE0716A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 69 2 Principal Parts and Functions 70 ...
Страница 77: ... 68 ...
Страница 83: ... 74 ...
Страница 85: ... 76 ...
Страница 109: ... 100 ...
Страница 125: ... 116 ...
Страница 220: ... 211 HWE0716A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 213 ...
Страница 221: ... 212 ...
Страница 265: ......