VI
Refrigerant Circuit ]
- 72 -
HWE0716A
GB
Solenoid
valve
SV1a
Discharge-
suction
bypass
1) High/low pressure bypass at
start-up and stopping, and ca-
pacity control during low-load
operation
2) High-pressure-rise prevention
AC208-230V
Open while being powered/
closed while not being pow-
ered
Continuity
check with a
tester
SV2
High/low pressure bypass at heat-
ing startup in low temperature or at
resuming operation after the com-
pletion of the defrost cycle
SV6
Changes bypass flow path from liq-
uid pipe (or 2-phase liquid pipe) on
the outdoor unit
1) High/low pressure bypass at
heating startup in low tempera-
ture or at resuming operation
after the completion of the de-
frost cycle
2) Capacity control during low-
load heating operation
SV9
Linear ex-
pansion
valve
LEV1
(SC control)
Adjusts the amount of bypass flow
from the liquid pipe on the outdoor
unit during cooling
DC12V
Opening of a valve driven by
a stepping motor 0-480 puls-
es (direct driven type)
Same as in-
door LEV
The resistance
value differs
from that of the
indoor LEV.
(Refer to the
section "LEV
Troubleshooti
ng."(page 192
))
LEV2a
LEV2b
(Refrigerant
flow adjust-
ment)
Adjusts refrigerant flow during heat-
ing
DC12V
Opening of a valve driven by
a stepping motor 1400 puls-
es
Same as in-
door LEV
LEV4
Opening and closing control of in-
jection circuit
DC12V
Degree of stepping motor
valve closing 0 - 480 pulses
(direct driven type)
Same as LEV1
Heater
CH11
Heats the refrigerant in the com-
pressor
Cord heater AC208/230V
CH11: 928ohm (230V)
Resistance
check
4-way valve
21S4a
Changeover between heating and
cooling
AC208-230V
Dead: cooling cycle
Live: heating cycle
Continuity
check with a
tester
Part name
Symbols
(functions)
Notes
Usage
Specifications
Check method
Содержание City Multi PUHY-HP144TSHMU-A
Страница 1: ......
Страница 9: ...HWE0716A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 53: ... 44 ...
Страница 63: ... 54 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 76: ... 67 HWE0716A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 69 2 Principal Parts and Functions 70 ...
Страница 77: ... 68 ...
Страница 83: ... 74 ...
Страница 85: ... 76 ...
Страница 109: ... 100 ...
Страница 125: ... 116 ...
Страница 220: ... 211 HWE0716A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 213 ...
Страница 221: ... 212 ...
Страница 265: ......