VII
Control ]
- 85 -
HWE0716A
GB
(3) Bypass solenoid valve (SV6) (ON = Open)
If outdoor temperature (TH7) during heating operation is between 3°C[37°F] and 5°C[41°F] , ON or OFF.
(4) Bypass solenoid valve (SV9) (ON = Open)
Operation
SV6
ON OFF
During cooling operation
ON
During heating operation (outdoor tempera-
ture (TH7) is 5°C[41°F] and above)
Always ON except for the defrost cycle.
During heating operation (outdoor tempera-
ture (TH7) is 3°C[37°F] or below)
OFF when 1 minute has passed since compressor startup.
Operation
SV9
ON OFF
After resuming operation after the comple-
tion of the defrost cycle
ON for 5 minutes.
At NO1 compressor startup (outdoor tem-
perature: -15°C[5°F] or lower) or after re-
suming operation after the completion of the
defrost cycle(outdoor temperature:
-15°C[5°F] or lower)
ON when 5 minutes or less have
passed and 63HS1 or 2 < 1.76MPa
[255 psi].
OFF when 5 minutes or more have
passed or 63HS1 or 2
1.76MPa
[255 psi].
When the compressor stops at cooling/heat-
ing mode
ON for only 5 minutes in 1 hour.
During heating operation, during compres-
sor frequency Fmin operation, and when
high pressure (63HS1 or 2) rises
When 63HS1, 63HS2 exceeds
3.43 MPa [497 psi].
When 30 seconds have passed,
compressor frequency Fmin +10 or
more, and 2.65MPa [384 psi] or
less.
Содержание City Multi PUHY-HP144TSHMU-A
Страница 1: ......
Страница 9: ...HWE0716A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 53: ... 44 ...
Страница 63: ... 54 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 76: ... 67 HWE0716A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 69 2 Principal Parts and Functions 70 ...
Страница 77: ... 68 ...
Страница 83: ... 74 ...
Страница 85: ... 76 ...
Страница 109: ... 100 ...
Страница 125: ... 116 ...
Страница 220: ... 211 HWE0716A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 213 ...
Страница 221: ... 212 ...
Страница 265: ......