IX
Troubleshooting ]
- 191 -
HWE0716A
GB
(4) In case of SV6 (Bypass valve)
This solenoid valve opens when powered (Relay ON).
1) This valve turns on during cooling operation, during heating operation when the outside temperature is 5°C[41°F] or above,
or for one minute after resuming operation after the completion of defrost cycle.
2) Proper operation can be verified on the LED and by listening for the operation sound.(page 85)
3) Refrigerant flows through this valve during cooling operation (not during heating operation), so the operation status can be
verified by checking the temperature of the bypass circuit or by listening for the operation sound of the valve.
Do not give an impact from outside, as the outer hull will be deformed leading to the malfunction of the inner valve.
(5) In case of SV9 (Bypass valve)
This solenoid valve opens when powered (Relay ON).
1) This valve turns on for five minutes after resuming operation after the completion of defrost cycle. Proper operation can be
verified with the LED or by listening for the closing sound of the valve.
2) Proper operation can be verified on the LED and by listening for the operation sound.(page 85)
3) The operation status can be verified by checking the temperature of the bypass circuit or by listening for the operation sound
of the valve.
Do not give an impact from outside, as the outer hull will be deformed leading to the malfunction of the inner valve.
-4- Outdoor Unit Fan
To check the revolution of the fan, check the inverter output state on the self-diagnosis LED, as the inverter on the outdoor
fan controls the revolutions of the fan.The revolution of the fan is approximately 680rpm at full speed.
When starting the fan, the fan runs at full speed for 5 seconds.
When setting the DIP SW1 as shown in the figure below, the inverter output [%] will appear. 100% indicates the full speed
and 0% indicates the stopping.
As the revolution of the fan changes under control, at the interphase or when the indoor unit operation capacity is low, the
revolution of the fan may change.
If the fan does not move or it vibrates, Fan board problem or fan motor problem is suspected. Refer to - 6 - (2) [5] "Check the
fan motor ground fault or the winding."(page 199) and - 6 - (2) [6] "Check the Fan board failure."(page 199)
1 2 3 4 5 6 7 8 9 10
ON
SW1
Содержание City Multi PUHY-HP144TSHMU-A
Страница 1: ......
Страница 9: ...HWE0716A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 53: ... 44 ...
Страница 63: ... 54 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 76: ... 67 HWE0716A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 69 2 Principal Parts and Functions 70 ...
Страница 77: ... 68 ...
Страница 83: ... 74 ...
Страница 85: ... 76 ...
Страница 109: ... 100 ...
Страница 125: ... 116 ...
Страница 220: ... 211 HWE0716A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 213 ...
Страница 221: ... 212 ...
Страница 265: ......