- 109 -
Note 1 :
•
Board connector CN10 corresponds to TH11, 12 while connector
CN11 corresponds to TH15 through TS15. Remove the applicable connector
and check the sensor for each number.
Note 2, 3 :
1. Pull the sensor connector from the I/O board. Do not pull on the lead wire.
2. Measure resistance using a tester or other instrument.
3. Compare measured values with values on the graph below. A value within a range of
±
10% is normal.
Resistance measurement point (connector)
Temperature sensor resistance (graph)
Note 4 :
•
Check using LED monitor display switch (outdoor MAIN board SW1)
Measured Data
Signal
SW1 Setting
Remarks
Liquid inlet
temperature
TH11
See converter.
Bypass outlet
temperature
TH12
See converter.
Bypass outlet
temperature
TH15
See converter.
Bypass inlet
temperature
TH16
See converter.
Touch the probes of the tester or other instrument
to the shaded areas to measure.
Thermistor R
o
=15 k
Ω
Rt=15exp 3460 ( – )
1
273+t
1
273t
Resistance value
(k
Ω)