Mode
Connection
2000
Superheat
control
❇
1
60
Differential
Pressure control
❇
2
2000
60
LEV1
LEV3
❇
1
❇
2
❇
3
Superheat
control
Differential
pressure control
–
Control every minute so that superheat amount detected by bypass inlet and oulet
temperatures (TH12, TH15) stay in the specified range.
Control every minute so that detected differential pressure (PS1, PS3) stay in the
specified range.
60 or more pulses are sometimes detected because of rise in liquid side pressure (PS1).
• Liquid level
control
❇
3
• Differential
pressure control
❇
2
60
Differential
Pressure control
❇
2
[2] Control of BC Controller
(1)
Control of SVA, SVB and SVC
SVA, SVB and SVC are turned on and off depending on connection mode.
Cooling
Heating
Stop
Defrost
SVA
ON
OFF
OFF
OFF
SVB
OFF
ON
OFF
OFF
SVC
ON
OFF
OFF
OFF
(2)
Control of LEV
LEV opening (sj) is controlled corresponding to operation mode as follows:
(Number of pulse)
Operation mode
Cooling-only
Heating-only
Cooling-main
Heating-main
Stop
❇
Please confirm that the above parts of BC controllers are color-corded and shown with the name plate inside
the BC controller unit.
- 61 -
Содержание CITY MULTI CMB-P1016V-F
Страница 17: ...FANCON board CNFAN CNPOW CNFC2 CN15V1 CNDR1 CNIPM1 G A board Terminal for signal grounding CNDC1 CNDC2 16 ...
Страница 18: ... 17 RELAY 10 board RELAY 4 board ...
Страница 19: ... 18 BC controller SW4 SW5 SW2 SW1 CN12 Power supply 1 EARTH 3 N 5 L CN02 M NET transmission CN03 CNTR ...
Страница 72: ... 71 ...