1
PU(H)Y-(P)200·250·315
No SW
Item
LED
0000~9999
0000~9999
0000~9999
Remarks
1 2 3 4 5 6 7 8 9 0
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
0 0 0 0 0 0 0 0 0 0 0 Relay output display 1
(lighting to display)
Compressor
operation
Compressor
operation
52C1
Lights for
norman
operation
Chech display 1OC
Error
1 1 0 0 0 0 0 0 0 0 0 Check display 2
( including the IC)
2 0 1 0 0 0 0 0 0 0 0 Relay output display 2
(lights up to display)
SV1
SV3
SV4
3 1 1 0 0 0 0 0 0 0 0 Relay output display 3
(lights up to display)
CH1
4 0 0 1 0 0 0 0 0 0 0 Relay output display 4
Communication demand
capacity
External signal
(lights up to display)
21S4a
5 1 0 1 0 0 0 0 0 0 0
6 0 1 1 0 0 0 0 0 0 0
7 1 1 1 0 0 0 0 0 0 0
If no demand control ,
"--" is diaplayed.
8 0 0 0 1 0 0 0 0 0 0
Snow
sensor
Comp
ON/OFF
Night
mode
Active
filter
operation
Vacuum
operation
protection
delayed
Active filter
preliminary
error
3 minutes.
restart after
instantaneous
power
failure
Active filter
error
9 1 0 0 1 0 0 0 0 0 0 Outdoor unit
operation display
Warm up
mode
3 minutes
restart
protection
mode
Compressor
operation
Preliminary
error
error
10 0 1 0 1 0 0 0 0 0 0 Indoor unit check
Unit No 1
Unit No2
Unit No3
Unit No4
Unit No5
Unit No6
Unit No7
Unit No8
11 1 1 0 1 0 0 0 0 0 0
Unit No9
Unit No10 Unit No11 Unit No12 Unit No13 Unit No14 Unit No15 Unit No16
12 0 0 1 1 0 0 0 0 0 0
13 1 0 1 1 0 0 0 0 0 0
14 0 1 1 1 0 0 0 0 0 0 Indoor unit operation mode
Unit No 1
Unit No2
Unit No3
Unit No4
Unit No5
Unit No6
Unit No7
Unit No8
15 1 1 1 1 0 0 0 0 0 0
Unit No9
Unit No10 Unit No11 Unit No12 Unit No13 Unit No14 Unit No15 Unit No16
16 0 0 0 0 1 0 0 0 0 0
17 1 0 0 0 1 0 0 0 0 0
18 0 1 0 0 1 0 0 0 0 0 Indoor unit thermostat ON
Unit No 1
Unit No2
Unit No3
Unit No4
Unit No5
Unit No6
Unit No7
Unit No8
19 1 1 0 0 1 0 0 0 0 0
Unit No9
Unit No10 Unit No11 Unit No12 Unit No13 Unit No14 Unit No15 Unit No16
20 0 0 1 0 1 0 0 0 0 0
21 1 0 1 0 1 0 0 0 0 0
22 0 1 1 0 1 0 0 0 0 0
Defrost
Oil
recovery
Low
frequency
oil
collection
23 1 1 1 0 1 0 0 0 0 0 Outdoor unit operation mode Permissable
stop
Standby
Defrost
Cooling
Heating
Demand
24 0 0 0 1 1 0 0 0 0 0 Outdoor unit
control mode
Initial start Cooling
Refrigerant Refrigerant
Heating
25 1 0 0 1 1 0 0 0 0 0 Outdoor unit
preliminary error
High
pressure
error 1
Low
pressure
Error
Discharge
temperature
26 0 1 0 1 1 0 0 0 0 0
Overcurrent
protection
Heat sink
thermostat
operating
Overcurrent
break
Inverter
error
If there is no Error "--"
is displayed.
Lights up if an
abnormal stop has
occurres in the IC.
The indicator for unit
No1 goes off when
error reset is carried
out.
Lights up during
cooling . Blinks
during heating. Goes
off during stop and
blower mode.
Lights up when
thernostat is on.Goes
off when thermostat
is off.
(Address and error code reversed)
(Address and error code reversed)
LD8 is a relay output which
lights up at all times when
the micro computers power
is on. When sending off a
monitering request to IC is
terminated if there is no
error "----" is displayed.
- 145 -