- 81 -
❇
Connector connection specifications on the pressure sensor body side.
The connector’s pin numbers on the pressure sensor body side differ from the pin numbers on the main circuit board
side.
Sensor Body Side
MAIN Board Side
Vcc
Pin 1
Pin 3
Vout
Pin 2
Pin 2
GND
Pin 3
Pin 1
Solenoid Valve (SV1, 3, 4 for PU(H)Y-P200·250·315, SV1 for PU(H)Y-200·250·315)
Check if the control board’s output signals and the operation of the solenoid valves match.
Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to
the LED’s.
Each LED shows whether the relays for the following parts are ON or OFF. When a LED lights up, it indicates that the
relay is ON.
1) In the case of SV1 (Bypass Valve)
(a) When the compressor starts, SV1 is ON for 4 minutes, check operation by whether the solenoid valve is emitting
an operating noise.
(b) Changes in the oper
(c) SV1 goes on in accordance with the rise in high pressure in the cooling and heating mode, check operation
by LED display and the operating noise emitted by the solenoid valve.
ating condition by solenoid valve operation can be confirmed by the temperature of the
bypass circuit and the sound of the refrigerant.
1 2 3 4 5 6 7 8 9 10
ON
2) SV3, 4 (Control of heat exchanger capacity)
3) In the case of 21S4 (Multi-directional valve)
(a) Operations can be confirmed by LED display and operating sound of solenoid valve, because one or more of
SV3, 4 are turned on depending on conditions during cooling-only operations.
(2)
Outdoor unit fan
LED Display
Fan
Stop Full speed
0 100
(3)
Multi-directional valve features
When power is OFF: Used as a conductor for the cooling circuit between the oil separator outlet and heat
exchanger, and the gas-ball valve (BV1) and accumulator.
When power is ON : Used as a conductor for the heating circuit between the oil separator and gas-ball valve, and
the heat exchanger and accumulator.
It is possible to determine whether the unit is functioning properly by checking from which point to which point the
current is flowing by monitoring the LED display, or by checking the temperature at the time at both the inlet and
outlet of the multi-directional valve. Do not to check the temperature of the oil separator by direct contact due to the
high temperature of the piping.
❇
Do not apply excessive external impact, as the valve will not function properly if the outer wall is deformed.
· The outdoor unit fan is phase control and controls the number of fan rotations. Confirm the number of rotations while
monitoring the output status of the phase control output at the LED. The fan rotates at approximately 600rpm at full
speed.
· Refer to the outdoor unit control section for details on fan control.
The fan operates at 100% for 5 seconds and then alternates between high and low pressure control.
Turn the self-diagnosis switch ON to , the phase
control output status at the LED display.
❇
There are times when the AK does not go as high as 100 when in night mode etc.
1
2
3
4
5
6
7
8
SW1
LED
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8 9 10
ON
Comp
operation
Comp
operation
SV1
SV3
SV4
52C1
lights
for normal
operation