11
6-SPt
-
Setpoint Parameters
Error Code
Problem
Remarks
Err 1
Internal hardware fault
A fault of the microprocessor and/or the input circuit has been detected. Return indicator for repair.
Err 2
Parameter list memory fault
One or more of set-up parameters has changed value due to possible electrical glitch or loss of power during
parameter save operation. (during “End” display) Verify all set-up parameters, exit parameter set-up mode and
cycle power to indicator to clear error. If error remains, return indicator for repair.
Err 3
Calibration memory fault
Verify calibration accuracy of indicator. If out of tolerance, re-calibrate the indicator. Otherwise, to clear error,
enter and exit parameter set-up mode and cycle power to indicator. If error remains, return indicator for repair.
Err 4
Analog output calibration memory fault Verify calibration accuracy of analog output. To clear error, enter and exit parameter set-up mode and cycle
power to indicator. If error remains, replace analog output card.
Err 5
Defective keypad
The indicator has detected one of the keypad switches is defective. Inspect keypad for signs of damage or
sticking. Cycle power to indicator to clear error. If error remains, return indicator for repair.
TROUBLESHOOTING
As part of the start-up procedure, the indicator performs a series of internal
self tests. If one or more of the diagnostic tests fails, indicator operation is
disabled and an error message is displayed. Press the
TARA
key to
acknowledge the error.
Refer to the error table below for the cause and remedy for the fault detected.
For further technical assistance, contact technical support at the appropriate
company numbers listed.
*
Select alternate list to program these values.
Installation Environment
The indicator should be installed in a location that does not exceed the
maximum operating temperature and provides good air circulation. The
minimum vertical clearance to allow proper ventilation is 1". Placing the unit
near devices that generate excessive heat should be avoided. Be sure to keep it
away from heat sources (ovens, furnaces, etc.), away from direct contact with
caustic vapors, oils, steams, or any other process by-products that may affect
proper operation.
Continuous exposure to direct sunlight may accelerate the aging process of
the bezel. The bezel should be cleaned only with a soft cloth and neutral soap
product. Do NOT use solvents.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of the unit.
EMC GUIDELINES
The indicator has been designed and tested to meet the requirements of EMC
Directive 89/336/EEC. However, successful installations depend upon several
factors. These include cable routing, termination of cable shields, associated
equipment, etc.
Installation
The indicator meets NEMA 4X/IP65 requirements for indoor use when
properly installed. The unit is intended to be mounted into an enclosed panel.
Prepare the panel cutout to the dimensions shown in the Dimensions drawing.
Remove the panel latch and cardboard sleeve from the unit and discard the
cardboard sleeve. Slide the panel gasket over the rear of the unit to the back of
the bezel. The unit should be installed fully assembled. Insert the unit into the
panel cutout. While holding the unit in place, push the panel latch over the rear
of the unit so that the tabs of the panel latch engage in the slots on the case. The
panel latch should be engaged in the forward most slot possible. To achieve a
proper seal, tighten the latch screws evenly until the unit is snug in the panel
(Torque to approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
b-6
000.00
SETPOINT SOURCE
SETPOINT VALUE (alternate)*
Src-n
nor
OUTPUT PANEL LIGHT
LIt-1
NO
STANDBY OPERATION
Stb-1
AUto
RESET ACTION
rSt-1
nor
OUTPUT LOGIC
out-1
0000.0
OFF TIME DELAY
tOF-1
0000.0
ON TIME DELAY
tON-1
000.02
SETPOINT HYSTERESIS
HYS-1
000.00
SETPOINT VALUE (main)
SP-1
OFF
ACTION FOR SETPOINT
ACt-1
USER SETTING
FACTORY
SETTING
PARAMETER
DISPLAY
000.00
SETPOINT VALUE (alternate)*
b-6
SETPOINT SOURCE
Src-4
nor
OUTPUT PANEL LIGHT
LIt-4
NO
STANDBY OPERATION
Stb-4
AUto
RESET ACTION
rSt-4
nor
OUTPUT LOGIC
out-4
0000.0
OFF TIME DELAY
tOF-4
0000.0
ON TIME DELAY
tON-4
000.02
SETPOINT HYSTERESIS
HYS-4
000.00
SETPOINT VALUE (main)
SP-4
OFF
ACTION FOR SETPOINT
ACt-4
USER SETTING
FACTORY
SETTING
PARAMETER
DISPLAY
000.00
SETPOINT VALUE (alternate)*
b-6
SETPOINT SOURCE
Src-3
nor
OUTPUT PANEL LIGHT
LIt-3
NO
STANDBY OPERATION
Stb-3
AUto
RESET ACTION
rSt-3
nor
OUTPUT LOGIC
out-3
0000.0
OFF TIME DELAY
tOF-3
0000.0
ON TIME DELAY
tON-3
000.02
SETPOINT HYSTERESIS
HYS-3
000.00
SETPOINT VALUE (main)
SP-3
OFF
ACTION FOR SETPOINT
ACt-3
USER SETTING
FACTORY
SETTING
PARAMETER
DISPLAY
000.00
SETPOINT VALUE (alternate)*
b-6
SETPOINT SOURCE
Src-2
nor
OUTPUT PANEL LIGHT
LIt-2
NO
STANDBY OPERATION
Stb-2
AUto
RESET ACTION
rSt-2
nor
OUTPUT LOGIC
out-2
0000.0
OFF TIME DELAY
tOF-2
0000.0
ON TIME DELAY
tON-2
000.02
SETPOINT HYSTERESIS
HYS-2
000.00
SETPOINT VALUE (main)
SP-2
OFF
ACTION FOR SETPOINT
ACt-2
USER SETTING
FACTORY
SETTING
PARAMETER
DISPLAY