OM-254915 Page 25
5-13. Connecting 3-Phase Input Power (Continued)
!
Installation must meet all National and
Local Codes - have only qualified
persons make this installation.
!
Disconnect and lockout/tagout input
power before connecting input
conductors from unit.
!
Always connect green or green/yellow
conductor to supply grounding terminal
first, and never to a line terminal.
See rating label on unit and check input volt-
age available at site.
For Three-Phase Operation
1
Input Power Cord Strain Relief
2
Input Power Cord
3
Disconnect Device (switch shown in
the OFF position)
4
Green Or Green/Yellow Grounding
Conductor
5
Disconnect Device Grounding Terminal
6
Input Conductors (L1, L2 And L3)
7
Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1, L2, and L3 to
disconnect device line terminals.
8
Over-Current Protection
Select type and size of over-current
protection using Section 5-11 (fused
disconnect switch shown).
Close and secure door on disconnect device.
Follow established lockout/tagout proced-
ures to put unit in service.