Pr
oduct Featur
es
Page 17
1.6 Heating Mode
1.6.1 Compressor Control
1) Reach the configured temperature
• If the following conditions are satisfied, the
compressor ceases operation.
• While calculated frequency(fb) is less than
minimum limit frequency(FminC).
• When protective time is more than or equal to ten
minutes.
• When T1 is higher than or equal to Tsc+
HDIFTEMP2.
Note: HDIFTEMP2 is EEPROM setting parameter. It is 2°C
usually.
• If one of the following conditions is satisfied, not
judge protective time.
• Compressor running frequency is more than test
frequency.
• When compressor running frequency is equal to
test frequency, T4 is more than 15°C or no T4 or T4
fault.
• Change setting temperature.
• Turbo or sleep function on/off.
2) When the current is higher than the predefined safe
value, surge protection is activated, causing the
compressor to cease operations.
1.6.2 Indoor Fan Control:
1) In heating mode, the indoor fan operates continuously.
The fan speed can be set to 1%-100%, or mute.
2) Auto fan
• Rise curve
• When T1-Tsc is higher than -1.5°C, fan speed
reduces to 80%;
• -When T1-Tsc is higher than 0°C, fan speed reduces
to 60%;
• -When T1-Tsc is higher than 0.5°C, fan speed
reduces to 40%;
• -When T1-Tsc is higher than 1°C, fan speed reduces
to 20%.
• Descent curve
• When T1-Tsc is lower than or equal to 0.5°C, fan
speed increases to 20%;
• -When T1-Tsc is lower than or equal to 0°C, fan
speed increases to 60%;
• -When T1-Tsc is lower than or equal to -1.5°C, fan
speed increases to 80%;
• -When T1-Tsc is lower than or equal to -3°C, fan
speed increases to 100%.
1.6.3 Outdoor Fan Control:
• The outdoor unit will be run at different fan speed
according to T4 and compressor running frequency.
• For different outdoor units, the fan speeds are
different.
1.6.4 Defrosting mode
• The unit enters defrosting mode according to changes
in the temperature value of T3, T4 as well as the
compressor running time.
• In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the “
” symbol is displayed.
• If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
• T3 rises above TCDE1
°C
.
• T3 maintained above TCDE2°C for 80 seconds.
• Unit runs for 15 minutes consecutively in defrosting
mode.
1.6.5 Evaporator Temperature Protection
When the evaporator temperature exceeds a preset
protection value, the compressor stops.
1.7 Auto-mode
• This mode can be selected with the remote controller
and the setting temperature can be changed between
16°C~30°C
.
• In auto mode, the machine selects cooling, heating,
auto-drying or fan-only mode on the basis of T1,Ts, T4
and relative humidity.
• If the setting temperature is modified, the machine
selects a new running function.
1.8 Drying mode
In drying mode, AC operates the same as auto fan in
cooling mode.
1) Mute function is active.
• All protections are activated and operate the same as
they do that in cooling mode.
2) Low Room Temperature Protection
• If the room temperature is lower than 10°C, the
compressor ceases operations and does not resume
Содержание MISSION2 3D INVERTER Series
Страница 1: ...MISSION2 3D INVERTER SERIES SM_MISSION2 GA _60R410A_3D INVERTER_US_NA_171121 2017 SERVICE MANUAL...
Страница 2: ......
Страница 4: ......
Страница 11: ...Specifications Page 7 MOB01 09HFN1 MW0W MOB01 12HFN1 MV0W MOCA01 18HFN1 MT0W...
Страница 12: ...Specifications Page 8 MOD01 23HFN1 MT0W...
Страница 15: ...Specifications Page 11 PCB board of MOD01 23HFN1 MT0W...
Страница 16: ...Specifications Page 12 IPM board of MOD01 23HFN1 MT0W...
Страница 101: ...Troubleshooting Page 97 Remark Measure the DC voltage between P and N port The normal value should be around 310V...